OSHA Inspection: GEORGIA POWER COMPANY

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of GEORGIA POWER COMPANY in 317 COVERED BRIDGE RD. SW PLANT BOWEN, CARTERSVILLE, GA 30120 (NAICS 221112). OSHA activity number 341348845.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Georgia Power Company for free Get an email when a new federal OSHA severe-injury report for Georgia Power Company is published. One employer, no account, unsubscribe in one click.
Site address
317 COVERED BRIDGE RD. SW PLANT BOWEN
City
CARTERSVILLE
State
GA
ZIP
30120
Mailing
317 COVERED BRIDGE RD. SW PLANT BOWEN, CARTERSVILLE, GA 30120
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
Employees
1000
Ownership type
Private (A)

4 citations on file for this inspection.

1910.269 A03 I C

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Sep 1, 2016
Abate by
Oct 20, 2016
Penalty
Initial $12,471 · Current $0 Reduced
29 CFR 1910.269(a)(3)(i)(C): Information about the design and operation of the host employer's installation that the contract employer needs to make the assessments required by this section;   a.  Unit 3, Cooling Tower - The host employer (Georgia Power) did not provide the contract employer (Fluor) electrical circuit drawings or other relevant information needed for determining whether conductors to be removed from Cooling Tower conduit were disconnected and de-energized. The failure to provide adequate circuitry information prevented the transfer of needed information such as the nominal voltage on lines and equipment to be removed during the Fluor demolition process.
Recent events (2)
  • · I (S) $0
  • · Z (S) $12471

1910.269 A04

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Sep 1, 2016
Abate by
Oct 20, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.269(a)(4): Extent of briefing. Existing characteristics and conditions. Existing characteristics and conditions of electric lines and equipment that are related to the safety of the work to be performed shall be determined before work on or near the lines or equipment is started. Such characteristics and conditions include, but are not limited to:  a.  Unit 3 Cooling Tower - Georgia Power did not provide Fluor management sufficient information for identifying conductor cables that were energized before the demolition project began.  The failure to provide adequate circuitry information prevented the Fluor employee in charge from a briefing transfer of needed information such as the nominal voltage on lines and equipment to be removed during the demolition process.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.269 D02 IV B

Deleted Repeat Gravity 10 1 instance 2 exposed
Issued
Sep 1, 2016
Abate by
Oct 20, 2016
Penalty
Initial $68,591 · Current $0 Reduced
29 CFR 1910.269(d)(2)(iv)(B): Specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy;  a.  Plant Bowen, Unit 3 Cooling tower - The employer did not develop and issue a specific clearance (tagout procedure) which included specific procedural steps necessary for working on the de-icing circuits for tower 3.  Georgia Power Company was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR 1910.269(d)(2)(iv)(B), which was contained in OSHA Inspection Number 900009, Citation Number 1, Item Number 6b and was affirmed as a final order on December 5, 2014, with respect to a workplace located at Plant Bowen, 317 Covered Bridge Rd SW, Cartersville GA 30120.
Recent events (2)
  • · I (R) $0
  • · Z (R) $68591

1910.269 D06 VII

Deleted Repeat Gravity 10 1 instance 2 exposed
Issued
Sep 1, 2016
Abate by
Oct 20, 2016
Penalty
Initial $68,591 · Current $0 Reduced
29 CFR 1910.269(d)(6)(vii): Before starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isolation and deenergizing of the machine or equipment have been accomplished. If normally energized parts will be exposed to contact by an employee while the machine or equipment is deenergized, a test shall be performed to ensure that these parts are deenergized.  a.  Plant Bowen, Engine Generator House 120/208 Distribution Panel - On or about February 19, 2016 the Georgia Power authorized employee(s) did not verify the absence of voltage prior to work starting on the circuits and equipment.  Georgia Power Company was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR 1910.269(d)(6)(vii), which was contained in OSHA Inspection Number 900009, Citation Number 1, Item Number 14b and was affirmed as a final order on December 5, 2014, with respect to a workplace located at Plant Bowen, 317 Covered Bridge Rd SW, Cartersville GA 30120.
Recent events (2)
  • · I (R) $0
  • · Z (R) $68591

View Georgia Power Company's full OSHA safety record →