ALLENTOWN, PA —
OSHA Inspection: MORGAN ADVANCED CERAMICS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MORGAN ADVANCED CERAMICS, INC. in 7331 WILLIAM AVE, ALLENTOWN, PA 18106 (NAICS 325180). OSHA activity number 341402881.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MORGAN ADVANCED CERAMICS, INC.
- Site address
- 7331 WILLIAM AVE
- City
- ALLENTOWN
- State
- PA
- ZIP
- 18106
- Mailing
- 7331 WILLIAM AVE, ALLENTOWN, PA 18106
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325180
- Employees
- 43
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.147 C04 I
- Issued
- May 25, 2016
- Penalty
- Initial $3,825 · Current $1,913 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) CMP Reactors 1-6, North West end of shop - on or about April 21, 2016, the employer developed written energy control procedure CMP Reactors 1-6 for the loading, unloading and cleaning of the machines, however, management did not utilize the procedure for energy control activities performed. b) GC5, South East end of shop - on or about April 21, 2016, the employer developed a written energy control procedure GC5 for maintenance of the machine, however, management did not utilize the procedure for energy control activities performed. c) GC6, South East end of shop - on or about April 21, 2016, the employer developed a written energy control procedure GC6 for maintenance of the machine, however, management did not utilize the procedure for energy control activities performed. d) GC7, South East end of shop - on or about April 21, 2016, the employer developed a written energy control procedure GC7 for maintenance of the machine, however, management did not utilize the procedure for energy control activities performed. e) Mill Lane, South West end of shop - on or about April 21, 2016, the employer developed a written energy control procedure Mill Lane for maintenance of the machine, however, management did not utilize the procedure for energy control activities performed. f) OPTO 2, North West end of shop - on or about April 21, 2016, the employer developed a written energy control procedure OPTO 2 for ion source work of the machine, however, management did not utilize the procedure for energy control activities performed.
Recent events (2)
- — I (S) $1912.5
- — Z (S) $3825
1910.147 C06 I C
- Issued
- May 25, 2016
- Abate by
- Jun 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i)(C): Where lockout was used for energy control, the periodic inspection did not include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected. a) Energy Control Program - on or about April 21, 2016, the employer performed periodic inspections for the energy control program which did not include a review between the inspector and each authorized employee.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 B02 I
- Issued
- May 25, 2016
- Abate by
- Jun 14, 2016
- Penalty
- Initial $3,060 · Current $1,530 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: a) 7331 William Ave. Allentown, PA - on or about April 21, 2016, the employer did not have a written copy of the procedures for lockout and tagging when working on or near exposed de-energized parts available.
Recent events (2)
- — I (S) $1530
- — Z (S) $3060
1910.333 B02 IV A
- Issued
- May 25, 2016
- Abate by
- Jun 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(A): Before circuits or equipment were worked as deenergized, a qualified person did not operate the equipment operating controls or otherwise verify that the equipment could not be restarted: a) 7331 William Ave. Allentown, PA - on or about April 21, 2016, employees performed electrical work on pressure chambers removing and installing heat lamp assemblies, but the employer did not ensure a qualified person verified that the equipment could not be restarted prior to working as de-energized.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 B02 IV B
- Issued
- May 25, 2016
- Abate by
- Jun 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that they were deenergized. a) 7331 William Ave. Allentown, PA - on or about April 21, 2016, employees performed electrical work on pressure chambers removing and installing heat lamp assemblies, but a qualified person did not use test equipment to test the circuit elements and electrical parts to verify that they were de-energized.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Morgan Advanced Ceramics, INC.
View Morgan Advanced Ceramics, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 325180)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341402881.