OSHA Inspection: DRUG ENFORCEMENT ADMINISTRATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DRUG ENFORCEMENT ADMINISTRATION in 8195 SUB BASE CHINNERY BUILDING, ST THOMAS, VI 00802 (NAICS 922120). OSHA activity number 341407286.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Drug Enforcement Administration — free Get an email when a new federal OSHA severe-injury report for Drug Enforcement Administration is published. One employer, no account, unsubscribe in one click.
Site address
8195 SUB BASE CHINNERY BUILDING
City
ST THOMAS
State
VI
ZIP
00802
Mailing
8195 SUB BASE CHINNERY BUILDING, ST THOMAS, VI 00802
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922120
Employees
25
Ownership type
D

6 citations on file for this inspection.

1910.37 A04

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 7, 2016
Abate by
Sep 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:   On or about 4/12/16, third floor area, an emergency exit light fixture will not turn on when tested.    PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 9 instances 5 exposed
Issued
Sep 7, 2016
Abate by
Sep 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   a) On or about 4/12/16, in the Communications Room area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  b) On or about 4/12/16, in the workstation next to the evidence room, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  c) On or about 4/12/16, in the Task Force Officer workstation next to the Administrative Assistant area, two (2) relocatable power taps  were not directly connected to a permanently installed branch circuit receptacle.  d) On or about 4/12/16, in the RAC office area, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.  e) On or about 4/12/16, in the IRS office area, two (2) relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.  f) On or about 4/12/16, in the IRS office area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  g) On or about 4/12/16, in the Receptionist office area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  h) On or about 4/12/16, in the workstation next to the Title 3 room, two (2) relocatable power tap were not directly connected to a permanently installed branch circuit receptacle.  i) On or about 4/12/16, in the workstation next to the Title 3 room, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.  j) On or about 4/12/16, in the Account Monitor office area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.303 G01

Serious Gravity 5 1 instance 9 exposed
Issued
Sep 7, 2016
Abate by
Sep 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  On or about 4/12/16, in the Electrical Room area, an electrical service panel was not readily accessible, the service panel was blocked by two stepladders.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 2 instances 1 exposed
Issued
Sep 7, 2016
Abate by
Sep 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a) On or about 4/12/16, in the Electrical Room area, two (2) circuit breaker panels had spaces between breakers that were not covered.  b) On or about 4/12/16, in the Electrical Room area, an electrical pull box had an opening on the side that was not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 4 instances 4 exposed
Issued
Sep 7, 2016
Abate by
Sep 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a) On or about 4/12/16, in the electrical room area, an electrical pull box was not covered or closed.  b) On or about 4/12/16, outside the Senior TFO area, an electrical outlet box was not covered or closed.  c) On or about 4/12/16, in the Deputy Director office area, an electrical outlet box was not covered or closed.  d) On or about 4/12/16, in the Title 3 room area, an electrical outlet box was not covered or closed.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.157 E03

Other-than-serious 1 instance 3 exposed
Issued
Sep 7, 2016
Abate by
Sep 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On or about 4/12/16, throughout the facility, the portable fire extinguishers were not maintained annually.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (O) $0

View Drug Enforcement Administration's full OSHA safety record →