Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: BUFFALO FREEZER AND COLD STORAGE LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUFFALO FREEZER AND COLD STORAGE LLC in 205 PINE ROAD, HAMMONTON, NJ 08037 (NAICS 493120). OSHA activity number 341414522.

Watch Buffalo Freezer AND Cold Storage LLC — free Get an email when a new federal OSHA severe-injury report for Buffalo Freezer AND Cold Storage LLC is published. One employer, no account, unsubscribe in one click.
Site address
205 PINE ROAD
City
HAMMONTON
State
NJ
ZIP
08037
Mailing
205 PINE ROAD, HAMMONTON, NJ 08037
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
20
Ownership type
A

3 citations on file for this inspection.

1910.132 A

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $840.00 Reduced
29 CFR 1910.132(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided, used, and maintained in a sanitary and reliable condition wherever it is necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact.  a) Buffalo Freezer and Cold storage LLC - Forklift maintenance area:  Employees were exposed to chemical burns while adding water to the forklift battery on a daily basis without using proper personal protective equipment such as goggles, chemical resistant gloves and apron.  Occurred on or about 04/12/2016.
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200

1910.151 C

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $840.00 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  a) Buffalo Freezer and Cold storage LLC - Forklift maintenance area:  The employer did not provide an eye wash station that provides 15 minutes of continue flow for flushing of the eyes when employees can come in contact with corrosive chemicals such as battery acid from filling the battery with water on a daily basis.  Occurred on or about 04/12/2016.
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200

1910.305 B01 II

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $840.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a)Buffalo Freezer and Cold Storage LLC - Warehouse in front of bay doors: An electrical panel powering equipment and lights in the facility had missing circuit breaker, observed on or about 04/12/2016.
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200