NEWTON, IL ·
OSHA Inspection: ILLINOIS POWER GENERATING COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ILLINOIS POWER GENERATING COMPANY in 6725 NORTH 500TH STREET, NEWTON, IL 62448 (NAICS 221112). OSHA activity number 341453850.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ILLINOIS POWER GENERATING COMPANY
- Site address
- 6725 NORTH 500TH STREET
- City
- NEWTON
- State
- IL
- ZIP
- 62448
- Mailing
- 6725 NORTH 500TH STREET, NEWTON, IL 62448
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221112
- Employees
- 121
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1910.146 D02
- Issued
- Jul 27, 2016
- Abate by
- Aug 22, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.146(d)(2): Under the permit-required confined space program required by 29 CFR 1910.146(c)(4), the employer did not identify and evaluate the hazards of permit spaces before employees entered: a) On or about April 28, 2016, as the controlling employer, Illinois Power Generating Company failed to identify and evaluate the potential gravity and spring energy of the 2E Coal Mill Journal Assembly prior to employees of Hi Tech Industrial Services, Inc. entering the permit required-confined space of the 2E Coal Mill.
Recent events (3)
- · F (S) $0
- · C (S) $7000
- · Z (S) $7000
1910.269 D02 III
- Issued
- Jul 27, 2016
- Abate by
- Aug 22, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(d)(2)(iii): Procedures were not developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section: a) On or about April 28, 2016, As the controlling employer, Illinois Power Generating Company failed to develop, document and use procedures to control hazardous energy such as potential gravity and spring energy of the 2E Coal Mill Journal Assembly. Employees of its subcontractor, Hi Tech Industrial Services, Inc. were exposed to the unexpected movement of the Journal Mill Wheel assembly during cleaning of the 2E Coal Mill.
Recent events (3)