Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TEX-CAP ELECTRIC, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of TEX-CAP ELECTRIC, INC. in 1260 SNOW POINT ROAD CHARLESTON NAVAL WEAPONS STATION, GOOSE CREEK, SC 29445 (NAICS 238210). OSHA activity number 341475002.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tex-Cap Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Tex-Cap Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1260 SNOW POINT ROAD CHARLESTON NAVAL WEAPONS STATION
City
GOOSE CREEK
State
SC
ZIP
29445
Mailing
P.O. BOX 202080, AUSTIN, TX 78720
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
30
Ownership type
A

3 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 5 exposed
Issued
Jun 28, 2016
Penalty
Initial $3,850 · Current $1,925 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) West wall of the Job Trailer:  A relocatable power tap designed and listed to provide power to high concentrations of low powered loads such as computers, TVs, stereos, printers etc., was used to provide power to high powered loads such as a Haier microwave oven; a Frigidaire compact refrigerator; and a Mr. Coffee coffee maker. This relocatable power tap was also found to be series connected (daisy chained) into another relocatable power tap which is also a violation of its' listing.
Recent events (2)
  • — I (S) $1925
  • — Z (S) $3850

1926.404 B02

Serious Gravity 5 1 instance 5 exposed
Issued
Jun 28, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.404(b)(2): Outlet devices had an ampere rating less than the load being served.  a) West wall of the Job Trailer: Two daisy chained relocatable power taps used to provide power to a Haier microwave oven; a Frigidaire compact refrigerator; and a Mr. Coffee coffee maker and ten (10) Retivis battery chargers with a total of 23.5 amps, was a larger amperage rating than the power taps' 15 amps.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.20 B02

Deleted Other-than-serious 1 instance 30 exposed
Issued
Jun 28, 2016
Abate by
Aug 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.20(b)(2): The employer did not initiate and maintain programs which provided for frequent and regular inspections of the job site, materials and equipment to be made by a competent person(s).  a) On or about 05-11-2016 at 1260 Snow Point Road, Charleston Naval Weapons Station, site inspections were not being performed on a frequent and regular basis ensuring safety and health hazards were identified and corrected in a timely manner.  NOTE:  "Competent Person" means one who is capable of identifying existing and predictable hazards in surroundings or working conditions which are unsanitary, hazardous, or dangerous to employees, and who has authorization to take prompt corrective measures to eliminate them.  ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Tex-Cap Electric, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341475002.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.