Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CLEAR PACK COMPANY DBA SONOCO CLEAR PACK

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CLEAR PACK COMPANY DBA SONOCO CLEAR PACK in 11610 COPENHAGEN COURT, FRANKLIN PARK, IL 60131 (NAICS 326199). OSHA activity number 341482305.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Clear Pack Company DBA Sonoco Clear Pack — free Get an email when a new federal OSHA severe-injury report for Clear Pack Company DBA Sonoco Clear Pack is published. One employer, no account, unsubscribe in one click.
Site address
11610 COPENHAGEN COURT
City
FRANKLIN PARK
State
IL
ZIP
60131
Mailing
11610 COPENHAGEN COURT, FRANKLIN PARK, IL 60131
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
151
Ownership type
A

5 citations on file for this inspection.

1910.303 G01 I A

Serious Gravity 1 3 instances 14 exposed
Issued
Oct 7, 2016
Abate by
Nov 28, 2016
Penalty
Initial $4,498 · Current $3,149 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:  (a) Main Building Lighting Transformer Area - On or about April 14, 2016, an electrical arc flash incident took place when the cover was being removed from the Olsen Electrics Corporation 330 kVA/460 VAC floor-mounted transformer and the cover fell into the energized conductors of the transformer.  A wall had been installed in the transformer area that partially blocked access to the right front side of the transformer and the cover's associated attachment hardware, not allowing a full 3 feet of working space for the entire width of the transformer.  (b) Main Building - Welding shop, access to the new Hammond Power Solutions 15 kVA/460 VAC transformer mounted to a structural column was blocked by the Colchester lathe, not allowing a full 3 feet of working space in front of the transformer.  (c) Main Building - Welding shop, access to two of three circuit breaker panels adjacent to the Hammond Power Solutions 15 kVA/460 VAC transformer was partially blocked by a metal 4-drawer cabinet and a pedestal-mounted grinder, not allowing a full 3 feet of working space in front of the circuit breaker panels.
Recent events (2)
  • — I (S) $3148.6
  • — Z (S) $4498

1910.303 G01 I B

Serious Gravity 1 1 instance 4 exposed
Issued
Oct 7, 2016
Abate by
Nov 28, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater :  (a)  Main building lighting transformer area - On or about April 14, 2016, an electrical arc flash incident took place when the cover was being removed from the Olsen Electrics Corporation 330 kVA/460 VAC floor-mounted transformer (48 inches wide) and the cover fell into the energized conductors of the transformer.  A wall had been installed in the transformer area that partially blocked access to the right front side of the transformer and the cover's associated attachment hardware, not allowing a 48-inch wide working space in front of the transformer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 I C

Serious Gravity 1 1 instance 14 exposed
Issued
Oct 7, 2016
Abate by
Nov 28, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303:  a) Main building lighting transformer area - On or about April 14, 2016, an electrical arc flash incident took place when the cover was being removed from the Olsen Electrics Corporation 330 kVA/460 VAC floor-mounted transformer and the cover fell into the energized conductors of the transformer.  A wall had been installed in the transformer area that partially blocked access to the right top side of the transformer, not allowing a full 6 foot 6 inch headroom work space for the entire width of the transformer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A01

Serious Gravity 5 1 instance 4 exposed
Issued
Oct 7, 2016
Abate by
Nov 28, 2016
Penalty
Initial $7,496 · Current $5,247 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:  (a) In the Main Building MCC Room - On or about April 14, 2016, an employee was exposed to electrical arc flash hazards while working on an energized transformer when the access cover fell onto the energized conductors inside the transformer's protective enclosure.
Recent events (2)
  • — I (S) $5247.2
  • — Z (S) $7496

1910.253 B05 II G

Other-than-serious 1 instance 14 exposed
Issued
Oct 7, 2016
Abate by
Oct 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(5)(ii)(G): Cylinder valves shall be closed when work is finished.  (a) Main Building Welding Shop - Oxy-Acetylene cutting/welding torch on a cart in the center of the shop was not in use and the oxygen tank had not been closed at the completion of its last use. Pressure on the regulators indicated over 1000 PSI on the inlet side and 80 PSI on the outlet side.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341482305.