PHILADELPHIA, PA ·
OSHA Inspection: HATZEL & BUEHLER, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of HATZEL & BUEHLER, INC. in 1919 MARKET STREET, PHILADELPHIA, PA 19103 (NAICS 238210). OSHA activity number 341495323.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HATZEL & BUEHLER, INC.
- Site address
- 1919 MARKET STREET
- City
- PHILADELPHIA
- State
- PA
- ZIP
- 19103
- Mailing
- TEN PENN CENTER 1801 MARKET STREET - SUITE 220, PHILADELPHIA, PA 19103
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 12
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1926.95 A
- Issued
- Nov 4, 2016
- Abate by
- Nov 10, 2016
- Penalty
- Initial $11,224 · Current $0 Reduced
General-duty citation text
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided a) Jobsite: Area 306/307 - Employees handling an energized electrical tray cable for a new light post installation were exposed to electrical shock hazards as the employer did not require the use of appropriate hand protective equipment. Noted on or about 5/16/16.
Recent events (2)
- · I (S) $0
- · Z (S) $11224
1926.416 A03
- Issued
- Nov 4, 2016
- Abate by
- Nov 10, 2016
- Penalty
- Initial $11,224 · Current $7,857 Reduced
General-duty citation text
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit. a) Jobsite: 2nd Floor, Rm #216 - An employee was exposed to an electrical hazard while handling energized conductors during the installation of a 2 x 2 lay in ceiling light fixture. Noted on or about 5/16/16.
Recent events (2)
- · I (O) $7856.8
- · Z (S) $11224
1926.417 C
- Issued
- Nov 4, 2016
- Abate by
- Nov 10, 2016
- Penalty
- Initial $11,224 · Current $7,317 Reduced
General-duty citation text
29 CFR 1926.417(c): Tags were not placed to identify plainly the equipment or circuits being worked on. a) Jobsite: 2nd floor, room 216 - An employee handling energized conductors during the installation of a 2 x 2 lay in ceiling light fixture was exposed to electrical shock hazards as the employer did not plainly tag the circuits being worked on. Noted on or about 5/16/16.
Recent events (2)
- · I (O) $7316.8
- · Z (S) $11224
More inspections at Hatzel & Buehler, INC.
View Hatzel & Buehler, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341495323.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.