OSHA Inspection: NORTHERN ILLINOIS GAS COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NORTHERN ILLINOIS GAS COMPANY in 20487 N 1700 EAST ROAD, HUDSON, IL 61748 (NAICS 221210). OSHA activity number 341538874.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Northern Illinois GAS Company — free Get an email when a new federal OSHA severe-injury report for Northern Illinois GAS Company is published. One employer, no account, unsubscribe in one click.
Site address
20487 N 1700 EAST ROAD
City
HUDSON
State
IL
ZIP
61748
Mailing
20487 N 1700 EAST ROAD, HUDSON, IL 61748
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
Yes
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221210
Employees
14
Ownership type
A

6 citations on file for this inspection.

1910.147 C04 II D

Other-than-serious 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Aug 19, 2016
Penalty
Initial $7,000 · Current $4,500 Reduced
29 CFR 1910.147(c)(4)(ii)(D): The energy control procedures did not clearly and specifically outline the requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control:    On or about May 18, 2016, employees performed maintenance activities on the Unit 12 South Gas Fan and the employer did not ensure the energy control procedures clearly documented and described the requirements for verifying the electrical energy and residual energy of the mechanical parts of the fan had been controlled.
Recent events (3)
  • — F (O) $4500
  • — C (S) $7000
  • — Z (S) $7000

1910.147 C06 I B

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Aug 19, 2016
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.147(c)(6)(i)(B): The periodic inspection of the energy control procedure was not conducted to correct any deviations or inadequacies:  On or about May 18, 2016, employees performed maintenance activities on the Unit 12 South Gas Fan and the employer did not ensure their periodic inspection of the equipment had identified the lack of process to verify zero energy state for electrical energy and the residual energy of the mechanical parts of the fan.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.147 C06 II

Other-than-serious 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Aug 19, 2016
Penalty
Initial $0 · Current $4,500
29 CFR 1910.147(c)(6)(ii): The periodic inspection certification of energy control procedures did not contain the required documentation on identification of the machine or equipment, the date of the inspection, the employees included in the inspection, and the name of the person that performed the inspection:    On or about May 18, 2016, employees performed maintenance activities on the Unit 12 South Gas Fan and the employer did not ensure a periodic inspection of the equipment was documented and included the identification of the equipment, the date of the inspection, the employees included in the inspection, and the name of the person that performed the inspection.
Recent events (3)
  • — F (O) $4500
  • — C (S) $0
  • — Z (S) $0

1910.147 C07 I

Other-than-serious 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Aug 19, 2016
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees:    On or about May 18, 2016, employees performed maintenance activities on the Unit 12 South Gas Fan and the employer did not ensure employees were provided training on the need for each employee to isolate and control the energy sources, understand how to verify the electrical energy has been controlled and properly use the testing equipment and the controls to be used for the residual energy of the mechanical parts of the equipment.
Recent events (3)
  • — F (O) $7000
  • — C (S) $7000
  • — Z (S) $7000

1910.147 F03 II D

Other-than-serious 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Aug 19, 2016
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.147(f)(3)(ii)(D): Each authorized employee did not affix a personal lockout or tagout device to the group lockout device before working on the machine or equipment:    On or about May 18, 2016, employees performed maintenance activities on the Unit 12 South Gas Fan and the employer did not ensure all of the employees applied a personal lockout device to the electrical energy source before working on the equipment.
Recent events (3)
  • — F (O) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.219 C03

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Aug 19, 2016
Penalty
Initial $4,000 · Current $0 Reduced
29 CFR 1910.219(c)(3): Vertical and inclined shafting seven (7) feet or less from floor or working platform, was not enclosed with a stationary casing in accordance with requirements of paragraphs (m) and (o) of this section.  On or about May 18, 2016, employees performed maintenance activities on the Unit 12 South Gas Fan and the vertical shafting less than seven feet from the ground was not enclosed as required by the standard.
Recent events (3)
  • — F (S) $0
  • — C (S) $4000
  • — Z (S) $4000

View Northern Illinois GAS Company's full OSHA safety record →