SAMSON, AL ·
OSHA Inspection: BROOKS PEANUT COMPANY, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BROOKS PEANUT COMPANY, INC. in 402 EAST MAIN STREET, SAMSON, AL 36477 (NAICS 115114). OSHA activity number 341543486.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BROOKS PEANUT COMPANY, INC.
- Site address
- 402 EAST MAIN STREET
- City
- SAMSON
- State
- AL
- ZIP
- 36477
- Mailing
- P.O. BOX 305, SAMSON, AL 36477
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 115114
- Employees
- 80
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
1910.303 G02 I
- Issued
- Jul 1, 2016
- Penalty
- Initial $2,529 · Current $1,600 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) At Warehouse Electrical Panel WH: On or about June 6, 2016 and at times prior; the employer exposed his employees to electrical hazards in that employees were allowed to work around open breaker slots exposing live 120 volt buss bar inside the electrical panel. b) At Rear Wall Outside Processing Plant: On or about June 6, 2016 and at times prior; the employer exposed his employees to electrical hazards in that employees were allowed to work around open breaker slots exposing live 120 - 240 volt buss bar inside the electrical panel. c) At Rear Wall Outside Processing Plant: On or about June 6, 2016 and at times prior; the employer exposed his employees to electrical hazards in that employees were allowed to work around open breaker slots exposing live 480 volt buss bar inside the electrical panel.
Recent events (2)
- · I (S) $1600
- · Z (S) $2529
More inspections at Brooks Peanut Company, INC.
View Brooks Peanut Company, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 115114)
More inspections in AL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341543486.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.