Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: SCHUFF STEEL COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SCHUFF STEEL COMPANY in 2001 N. DAVIS RD, OTTAWA, KS 66067 (NAICS 332312). OSHA activity number 341564060.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Schuff Steel Company for free Get an email when a new federal OSHA severe-injury report for Schuff Steel Company is published. One employer, no account, unsubscribe in one click.
Site address
2001 N. DAVIS RD
City
OTTAWA
State
KS
ZIP
66067
Mailing
2001 N DAVIS RD, OTTAWA, KS 66067
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
550
Ownership type
Private (A)

3 citations on file for this inspection.

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 1, 2016
Abate by
Aug 25, 2016
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:  On or about 11 June 2016, maintenance employees did not de-energize the Beam Line Siemens 277/480 V, 800 Amp breaker before doing maintenance work.  Employees were exposed to arc flash burn hazards.
Recent events (2)
  • · I (S) $7000
  • · Z (S) $7000

1910.335 A02 II

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Aug 1, 2016
Abate by
Aug 25, 2016
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee was working near exposed energized parts:      On or about 11 June 2016, maintenance employees were not wearing personal protective equipment such as gloves, face shield or other barriers when performing maintenance to the energized Beam Line  277/480V, 800 Amp breaker.  Employees were exposed to arc flash burn hazards.
Recent events (2)
  • · I (O) $0
  • · Z (S) $7000

1910.335 B01

Deleted Serious Gravity 1 1 instance 2 exposed
Issued
Aug 1, 2016
Abate by
Aug 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them as required by 29 CFR 1910.145:  On or about 11 June 2016, the breaker in which maintenance employees were working did not have any warning signs or symbols on the outside or inside of the Beam Line Siemens 277/480V, 800 Amp breaker panel to warn of arc flash hazards.   Employees were exposed to arc flash burn hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

View Schuff Steel Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341564060.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.