JERSEY CITY, NJ —
OSHA Inspection: JERSEY CITY MEDICAL CENTER RWJ BARNABAS HEALTH
Federal Agency inspection · Health discipline
At a glance
On , OSHA opened a federal Agency health inspection of JERSEY CITY MEDICAL CENTER RWJ BARNABAS HEALTH in 355 GRAND STREET, JERSEY CITY, NJ 07302 (NAICS 622110). OSHA activity number 341585891.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- JERSEY CITY MEDICAL CENTER RWJ BARNABAS HEALTH
- Site address
- 355 GRAND STREET
- City
- JERSEY CITY
- State
- NJ
- ZIP
- 07302
- Mailing
- 355 GRAND STREET, JERSEY CITY, NJ 07302
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 2000
- Ownership type
- A
Citations
7 citations on file for this inspection.
1903.19 D01
- Issued
- Mar 24, 2020
- Abate by
- Apr 6, 2020
- Penalty
- Initial $1,082 · Current $750 Reduced
General-duty citation text
29 CFR 1903.19(d)(1): The employer did not submit to the Agency documents demonstrating that abatement is complete for each willful or repeat violation and for any serious violation for which the Agency indicates in the citation that such abatement documentation is required: a) Facility The employer did not provide abatement certification and documentation for inspection number 1158589 Citation 1, Item 1 29 CFR 1910.333(a)(1), Citation 1 Item 2a 29 CFR 1910.333(b)(2), Citation 1 Item 2b 29 CFR 1910.333(b)(2)(i), Citation 1 Item 3 29 CFR 1910.333(c)(2), Citation 1 Item 4 29 CFR 1910.335(a)(1)(i), Citation 2 Item 1 29 CFR 1910.332(b)(1) which was issued to the employer on 12/21/2016. The citations became a final order on August 2, 2019. Violation occurred on or about March 6, 2020.
Recent events (2)
- — I (O) $750
- — Z (O) $1082
1910.333 A01
- Issued
- Dec 21, 2016
- Abate by
- Jan 19, 2017
- Penalty
- Initial $12,471 · Current $12,471
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee worked on or was near to them: a) Facility General maintenance mechanics work on live 277 volt AC while changing ballasts for overhead fluorescent lights. On or about 06/26/16, a worker performing such operations received an electrical shock while working from an A frame ladder. The worker fell approximately 6 ft. to the floor below, striking his head and later died of his injuries.
Recent events (3)
- — J (S) $12471
- — C (S) $12471
- — Z (S) $12471
1910.333 B02
- Issued
- Dec 21, 2016
- Abate by
- Jan 19, 2017
- Penalty
- Initial $12,471 · Current $12,471
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): a) ACC Building Room 231 While an employee was changing ballasts, the 277 volt circuits were not locked out or tagged after the toggle switch was turned off exposing the worker to electrocution. Violation occurred on or about 08/04/16.
Recent events (3)
- — J (S) $12471
- — C (S) $12471
- — Z (S) $12471
1910.333 B02 I
- Issued
- Dec 21, 2016
- Abate by
- Jan 19, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 and did not make it available for inspection by the Assistant Secretary of Labor and his or her authorized representatives: a) Facility The employer did not maintain written procedures for de-energizing 277 volt circuits for employees conducting electrical work such as changing ballasts. Violation occurred on or about 06/28/16.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.333 C02
- Issued
- Dec 21, 2016
- Abate by
- Jan 19, 2017
- Penalty
- Initial $12,471 · Current $12,471
General-duty citation text
29 CFR 1910.333(c)(2): Persons who were not qualified worked on electrical parts or equipment that had not been de-energized under the procedures of paragraph (b) of this section. Such persons were not capable of working safely on energized circuits and were not familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools: a) Facility The employer did not ensure that general maintenance mechanics performing live electrical work, such as changing ballasts on 277 volt circuits, were qualified to do such work. Violation occurred on or about 06/26/16.
Recent events (3)
- — J (S) $12471
- — C (S) $12471
- — Z (S) $12471
1910.335 A01 I
- Issued
- Dec 21, 2016
- Abate by
- Jan 19, 2017
- Penalty
- Initial $12,471 · Current $12,471
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with, or did not use, electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a) Facility General maintenance mechanics were not provided with appropriate hand protection such as rubber insulating gloves while performing live electrical work including, but not limited to, changing ballasts which operate at 277 volts. Violation occurred on or about 06/26/16.
Recent events (3)
- — J (S) $12471
- — C (S) $12471
- — Z (S) $12471
1910.332 B01
- Issued
- Dec 21, 2016
- Abate by
- Jan 19, 2017
- Penalty
- Initial $124,709 · Current $124,709
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) Facility The employer did not ensure that general maintenance mechanics were trained in safety-related work practices for electrical work such as, but not limited to, changing ballasts. An employee performing such operations received an electrical shock while working from an A frame ladder. The worker fell approximately 6 ft. to the floor below, striking his head and later died of his injuries. Violation occurred on or about 06/26/16.
Recent events (3)
- — J (W) $124709
- — C (W) $124709
- — Z (W) $124709
More inspections at Jersey City Medical Center RWJ Barnabas Health
View Jersey City Medical Center RWJ Barnabas Health's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341585891.