Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: CONTANDA TERMINALS, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CONTANDA TERMINALS, LLC in 2701 TALLEYRAND AVENUE, JACKSONVILLE, FL 32206 (NAICS 493190). OSHA activity number 341595676.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Contanda Terminals, LLC for free Get an email when a new federal OSHA severe-injury report for Contanda Terminals, LLC is published. One employer, no account, unsubscribe in one click.
Site address
2701 TALLEYRAND AVENUE
City
JACKSONVILLE
State
FL
ZIP
32206
Mailing
2900 EASTALLEGHENY AVENUE, PHILADELPHIA, PA 19134
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493190
Employees
10
Ownership type
Private (A)

3 citations on file for this inspection.

1910.106 E05 V

Other-than-serious 1 instance 3 exposed
Issued
Dec 27, 2016
Abate by
Jan 17, 2017
Penalty
Initial $4,810 · Current $0 Reduced
29 CFR 1910.106(e)(5)(v): All plant fire protection facilities were not adequately maintained and periodically inspected and tested to make sure they were always in satisfactory operating condition, and they could serve their purpose in time of emergency.    a.   On or about June 29, 2016, at the isopropanol loading station, an Aqueous Film Forming Foam supply hose to the fixed fire suppression cannon was kinked and crushed, exposing employees to fire hazards in the event of ignition of the isopropanol.
Recent events (2)
  • · I (O) $0
  • · Z (S) $4810

1910.106 E06 II

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 27, 2016
Abate by
Jan 9, 2017
Penalty
Initial $6,013 · Current $5,412 Reduced
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected.    a.   On or about June 29, 2016, at Rail Spot 15, the Telone loading area, the upper tower bonding wire used to electrically interconnect the dispensing unit and rail cars was severely frayed and corroded.
Recent events (2)
  • · I (S) $5411.5
  • · Z (S) $6013

1910.37 B06

Other-than-serious 1 instance 4 exposed
Issued
Dec 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a.   On or about June 30, 2016, in the maintenance building, at the south emergency exit door, the exit sign for emergency egress was not illuminated.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341595676.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.