OSHA Inspection: U.S. DRUG ENFORCEMENT ADMINISTRATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. DRUG ENFORCEMENT ADMINISTRATION in 3013 ESTATE GOLDEN ROCK, SUITE 142, CHRISTIANSTED, VI 00820 (NAICS 922120). OSHA activity number 341622330.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Drug Enforcement Administration — free Get an email when a new federal OSHA severe-injury report for U.S. Drug Enforcement Administration is published. One employer, no account, unsubscribe in one click.
Site address
3013 ESTATE GOLDEN ROCK, SUITE 142
City
CHRISTIANSTED
State
VI
ZIP
00820
Mailing
3013 ESTATE GOLDEN ROCK, SUITE 142, CHRISTIANSTED, VI 00820
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922120
Employees
18
Ownership type
D

2 citations on file for this inspection.

1910.303 B02

Repeat Gravity 1 9 instances 5 exposed
Issued
Dec 5, 2016
Abate by
Dec 23, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) On or about 7/7/16, in the Resident Agent in Charge office area, two (2) relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.   b) On or about 7/7/16, in the Resident Agent in Charge office area, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.   c) On or about 7/7/16, in the server room #183 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   d) On or about 7/7/16, in the room #182 area, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.   e)  On or about 7/7/16, in the file room area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   f) On or about 7/7/16, in the workstation #2 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   g) On or about 7/7/16, in the workstation #4 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   h) On or about 4/12/16, in the ATF room area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   i) On or about 4/12/16, in the ATF room area, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.   j) On or about 4/12/16, in the HIDTA IT room area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.   The U.S. Drug Enforcement Administration was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 1096202, citation number 1, item number 1, and was affirmed as a final order on 01/12/2016, with respect to a workplace located at 606 Tito Castro Avenue, Suite 301, Ponce, PR 00716.
Recent events (1)
  • — Z (R) $0

1910.305 B02 I

Repeat Gravity 5 5 instances 3 exposed
Issued
Dec 5, 2016
Abate by
Dec 23, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a) On or about 7/7/16, in the server room #183 area, an electrical outlet box was not covered or closed.  b) On or about 7/7/16, in the room #182 area, an electrical outlet box was not covered or closed.  c) On or about 7/7/16, between workstation #1 and #2 area, an electrical outlet box was not covered or closed.  d) On or about 7/7/16, in the room #147 area, an electrical outlet box was not covered or closed.  e) On or about 7/7/16, in the room #148 area, an electrical junction box was not covered or closed.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.  The U.S. Drug Enforcement Administration was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(2)(i), which was contained in OSHA inspection number 1096202, citation number 1, item number 2, and was affirmed as a final order on 01/12/2016, with respect to a workplace located at 606 Tito Castro Avenue, Suite 301, Ponce, PR 00716.