Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: CENTERPOINT ENERGY HOUSTON ELECTRIC, LLC

Fatality or catastrophe inspection · Health discipline

On , OSHA opened a fatality or catastrophe health inspection of CENTERPOINT ENERGY HOUSTON ELECTRIC, LLC in 14403 WESTBURY CT., HOUSTON, TX 77084 (NAICS 221122). OSHA activity number 341642015.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Centerpoint Energy Houston Electric, LLC for free Get an email when a new federal OSHA severe-injury report for Centerpoint Energy Houston Electric, LLC is published. One employer, no account, unsubscribe in one click.
Site address
14403 WESTBURY CT.
City
HOUSTON
State
TX
ZIP
77084
Mailing
P.O. BOX 1700, HOUSTON, TX 77251
Inspection type
Fatality or catastrophe (M)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
2700
Ownership type
Private (A)

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 2 exposed
Issued
Sep 30, 2016
Abate by
Jun 11, 2018
Penalty
Initial $12,471 · Current $9,353 Reduced
OSH ACT of 1970 Section (5)(a)(1):     The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees:    An Employee working on o near exposed energized parts f electrical equipment was not adequately supervised during the performance of live work and was not equipped with the appropriate personal protective equipment prior to working on or near exposed energized parts of electrical equipment.    Among other methods, feasible and acceptable methods to correct the hazard include:    (1)    The tailboard and job briefing forms will be revised to require he identification of the hazards,    safety precautions, and PPE specific to each work location;    (2)    Additional raining will be provided discussing when a change in conditions requires a new tailboard briefing to be performed;    (3)   Training will be revised to reinforce the requirement to install protective covers when working on underground transformers;    (4)   The supervision requirements will be revised to require that an apprentice, within his second period or less, may only work on a two-man distribution line crew if he is under the direct control of a journeyman.    (5)   Direct control means that the apprentice may not perform any work on electrical apparatuses unless within reaching distance of a journeyman and each are using the PPE called for by the work being performed.
Recent events (3)
  • · R (S) $9353
  • · C (S) $12471
  • · Z (S) $12471

1910.269 L04 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Sep 30, 2016
Abate by
Oct 20, 2016
Penalty
Initial $12,471 · Current $0 Reduced
29 CFR 1910.269(l)(4)(i): The employer did not ensure that when an employee uses rubber insulating gloves as insulation from energized parts (under paragraph (l)(3)(iii)(A) of this section), the employee shall also use rubber insulating sleeves:  On or about July 23, 2016, in the yard of a residential home where an apprentice was exposed to electrical hazards while connecting drop lines into an underground residential distribution (URD) transformer without using insulating sleeves or other means of insulation from the energized parts.
Recent events (3)
  • · R (S) $0
  • · C (S) $12471
  • · Z (S) $12471

1910.269 L05 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Sep 30, 2016
Abate by
Oct 20, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.269(l)(5)(i): The employer did not ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, un-insulated parts energized at a potential different from the employee's.  On or about July 23, 2016, in the yard of a residential home where an apprentice was exposed to electrical hazards while connecting drop lines into an underground residential distribution (URD) transformer without working in a position that prevented the employee from contacting un-insulated parts.