OSHA Inspection: RKB ELECTRIC & SUPPLY, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of RKB ELECTRIC & SUPPLY, LLC in 1030 5TH AVENUE, PITTSBURGH, PA 15219 (NAICS 238210). OSHA activity number 341657526.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch RKB Electric & Supply, LLC — free Get an email when a new federal OSHA severe-injury report for RKB Electric & Supply, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1030 5TH AVENUE
City
PITTSBURGH
State
PA
ZIP
15219
Mailing
27 GARY STREET, CARNEGIE, PA 15106
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
6
Ownership type
A

2 citations on file for this inspection.

1926.403 B01 VII

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 1, 2016
Penalty
Initial $2,800 · Current $2,800
29 CFR 1926.403(b)(1)(vii): 1926.403(b)(1)(vii):   Safety of equipment was not determined on the basis of the following considerations: Other factors which contribute to the practical safeguarding of employees using or likely to come in contact with the equipment:   (a)  Jobsite, Basement Electrical Room:  On or about July 26, 2016, the employer selected 3/4 inch long self tapping, 5/16's bolts to secure the trough cover.   This trough contained energized conductors.  This condition created the possibility of the tip of a self tapping bolt to come in contact with the conductors inside its insulation.
Recent events (1)
  • — Z (S) $2800

1926.21 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 1, 2016
Abate by
Aug 11, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury:   (a)  Jobsite:  On or about July 26, 2016, the employer did not train employees in the recognition and avoidance of the potential hazards created by the protrusion of self tapping bolts into the interior space of wireways housing energized conductors.
Recent events (1)
  • — Z (S) $0

View RKB Electric & Supply, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341657526.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.