Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AMERICOLD LOGISTICS LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AMERICOLD LOGISTICS LLC in 264 FARRELL ROAD, SYRACUSE, NY 13209 (NAICS 493120). OSHA activity number 341661957.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Americold Logistics LLC — free Get an email when a new federal OSHA severe-injury report for Americold Logistics LLC is published. One employer, no account, unsubscribe in one click.
Site address
264 FARRELL ROAD
City
SYRACUSE
State
NY
ZIP
13209
Mailing
264 FARRELL ROAD, SYRACUSE, NY 13209
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
30
Ownership type
A

5 citations on file for this inspection.

1910.303 B07 IV

Deleted Serious Gravity 1 2 instances 5 exposed
Issued
Sep 7, 2016
Abate by
Sep 19, 2016
Penalty
Initial $4,543 · Current $0 Reduced
29 CFR 1910.303(b)(7)(iv): Electric equipment was not installed in a neat and workmanlike manner in that there were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:  a)  Bldg. 2, Door #17, on or about 8/1/16:  Flexible cord providing current to a dock light had several cuts in the outer jacket and was deteriorated.  b)  Bldg. 3, Door 61, on or about 8/1/16:  A dock light was broken away from the support bracket and hanging by its flexible cord.  Abatement certification must be submitted for this item.
Recent events (3)
  • — J (S) $0
  • — C (S) $4543
  • — Z (S) $4543

1910.304 G05

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Sep 7, 2016
Abate by
Sep 19, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a)  Bldg. 3, Door 61, on or about 8/1/16:  A dock light was not grounded in that the ground pin was missing from the plug end.  Abatement certification must be submitted for this item.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 G02 III

Deleted Serious Gravity 1 2 instances 2 exposed
Issued
Sep 7, 2016
Abate by
Sep 19, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a)  Bldg. 2, Between Door #4 and Door #5, on or about 8/1/16:  Flexible cord providing current to a dock light was not provided with strain relief.  b)  Bldg. 3, Door #53, on or about 8/1/16:  Flexible cord providing current to a dock light was not provided with strain relief.  Abatement certification must be submitted for these items.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.37 B04

Other-than-serious 1 instance 5 exposed
Issued
Sep 7, 2016
Abate by
Oct 12, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:  a)  Bldg. 2, 7000 Room, on or about 8/1/16:  There were no exit directional signs provided to indicate the direction of travel to the nearest exit.  Abatement certification must be submitted for this item.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.157 G02

Deleted Other-than-serious 5 instances 5 exposed
Issued
Sep 7, 2016
Abate by
Oct 12, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter:  a)   At the establishment, on or about 8/1/16:  Annual training on the use of fire extinguishers had not been completed for five employees.  Abatement certification must be submitted for this item.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0