SYRACUSE, NY —
OSHA Inspection: AMERICOLD LOGISTICS LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of AMERICOLD LOGISTICS LLC in 264 FARRELL ROAD, SYRACUSE, NY 13209 (NAICS 493120). OSHA activity number 341661957.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMERICOLD LOGISTICS LLC
- Site address
- 264 FARRELL ROAD
- City
- SYRACUSE
- State
- NY
- ZIP
- 13209
- Mailing
- 264 FARRELL ROAD, SYRACUSE, NY 13209
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 30
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.303 B07 IV
- Issued
- Sep 7, 2016
- Abate by
- Sep 19, 2016
- Penalty
- Initial $4,543 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electric equipment was not installed in a neat and workmanlike manner in that there were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a) Bldg. 2, Door #17, on or about 8/1/16: Flexible cord providing current to a dock light had several cuts in the outer jacket and was deteriorated. b) Bldg. 3, Door 61, on or about 8/1/16: A dock light was broken away from the support bracket and hanging by its flexible cord. Abatement certification must be submitted for this item.
Recent events (3)
- — J (S) $0
- — C (S) $4543
- — Z (S) $4543
1910.304 G05
- Issued
- Sep 7, 2016
- Abate by
- Sep 19, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Bldg. 3, Door 61, on or about 8/1/16: A dock light was not grounded in that the ground pin was missing from the plug end. Abatement certification must be submitted for this item.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Sep 7, 2016
- Abate by
- Sep 19, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) Bldg. 2, Between Door #4 and Door #5, on or about 8/1/16: Flexible cord providing current to a dock light was not provided with strain relief. b) Bldg. 3, Door #53, on or about 8/1/16: Flexible cord providing current to a dock light was not provided with strain relief. Abatement certification must be submitted for these items.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.37 B04
- Issued
- Sep 7, 2016
- Abate by
- Oct 12, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: a) Bldg. 2, 7000 Room, on or about 8/1/16: There were no exit directional signs provided to indicate the direction of travel to the nearest exit. Abatement certification must be submitted for this item.
Recent events (3)
- — J (O) $0
- — C (O) $0
- — Z (O) $0
1910.157 G02
- Issued
- Sep 7, 2016
- Abate by
- Oct 12, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter: a) At the establishment, on or about 8/1/16: Annual training on the use of fire extinguishers had not been completed for five employees. Abatement certification must be submitted for this item.
Recent events (3)
- — J (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Americold Logistics LLC
View Americold Logistics LLC's full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341661957.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.