ENGLEWOOD, CO —
OSHA Inspection: MERCURY TUBE PRODUCTS LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of MERCURY TUBE PRODUCTS LLC in 3211 WEST BEAR CREEK DR, ENGLEWOOD, CO 80110 (NAICS 339999). OSHA activity number 341666899.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MERCURY TUBE PRODUCTS LLC
- Site address
- 3211 WEST BEAR CREEK DR
- City
- ENGLEWOOD
- State
- CO
- ZIP
- 80110
- Mailing
- 3211 WEST BEAR CREEK DR, ENGLEWOOD, CO 80110
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 339999
- Employees
- 52
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.111 B16 II
- Issued
- Sep 28, 2016
- Abate by
- Nov 1, 2016
- Penalty
- Initial $5,300 · Current $2,650 Reduced
General-duty citation text
29 CFR 1910.111(b)(16)(ii): Electrical systems were not installed and maintained in accordance with subpart S of this part. 1) On August 3, 2016, and at prior times, electrical equipment such as control boxes, light switches, electrical outlets, lights, junction boxes, flexible cords, and fan motors located in the ammonia tank room were not rated for Class I division 2 locations.
Recent events (2)
- — I (S) $2650
- — Z (S) $5300
1910.212 A01
- Issued
- Sep 28, 2016
- Abate by
- Oct 25, 2016
- Penalty
- Initial $8,730 · Current $4,365 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: 1) On August 3, 2016, and at prior times, machine guarding was not provided to protect employees from ingoing nip points at the following locations: a) On the tube straightener machines where there were ingoing nip points where employees feed tube stock into a roller guide. b) On the mill machines where there were ingoing nip points on the tube rollers. c) On the Wizard machine where there was an ingoing nip point on the counter roller. d) On the final testing machine where there were ingoing nip points on the tube rollers.
Recent events (2)
- — I (S) $4365
- — Z (S) $8730
1910.242 B
- Issued
- Sep 28, 2016
- Abate by
- Oct 11, 2016
- Penalty
- Initial $3,180 · Current $1,590 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: 1) On August 3, 2016, and at prior times, two compressed air nozzles used for cleaning in the lathe department had pressures in excess of 30 p.s.i.
Recent events (2)
- — I (S) $1590
- — Z (S) $3180
1910.303 B01
- Issued
- Sep 28, 2016
- Abate by
- Oct 11, 2016
- Penalty
- Initial $4,240 · Current $2,120 Reduced
General-duty citation text
29 CFR 1910.303(b)(1): Electric equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: 1) On August 3, 2016, and at prior times, the electrical cord on a fan located in the tube straightener department had damaged insulation that was repaired with duct tape and did not meet the cords original insulating properties.
Recent events (2)
- — I (S) $2120
- — Z (S) $4240
1910.303 B02
- Issued
- Sep 28, 2016
- Abate by
- Oct 11, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: 1) On August 3, 2016, and at prior times, an outlet box designed for installation on a wall was used as an extension box on the end of a flexible cord located in the annealing department. The box was used to supply power to a fan in the tube straightener department.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02
- Issued
- Sep 28, 2016
- Abate by
- Oct 11, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: 1) On August 3, 2016, and at prior times, an electrical junction box located on a poll in the mill department did not have a cover.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Sep 28, 2016
- Abate by
- Oct 11, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided to prevent pull from being directly transmitted to joints or terminal screws: 1) On August 3, 2016, and at prior times, strain relief was not attached at the switch box and at the plug on the flexible cord for the deburring machine.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 339999)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341666899.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.