NORDLAND, WA —
OSHA Inspection: U.S. GEOLOGICAL SURVEY, WFRC MARROWSTONE MARINE FIELD STATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. GEOLOGICAL SURVEY, WFRC MARROWSTONE MARINE FIELD STATION in 616 MARROWSTONE POINT RD, NORDLAND, WA 98358 (NAICS 541710). OSHA activity number 341681351.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 616 MARROWSTONE POINT RD
- City
- NORDLAND
- State
- WA
- ZIP
- 98358
- Mailing
- 616 MARROWSTONE POINT RD, NORDLAND, WA 98358
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541710
- Employees
- 4
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.23 E02
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(e)(2): Stair rails did not consist of a top rail, intermediate rail and/or posts, with the vertical height not more than 34 inches (86.36 cm) nor less than 30 inches (76.2 cm) from upper surface of top rail to surface of tread in line with face of riser at forward edge of tread: a) Historic House; The stairs to the basement had a 39-40 inch high top rail and were missing an intermediate rail and/or posts. b) Historic House; The stairs to the entrance had a 36 inch high top rail and were missing an intermediate rail and/or posts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Office L-103; A white relocatable power tap was plugged into another white relocatable power tap, which powered chargers and Dell computer equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 E01
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: a) Baker Lab; An outdoor outlet was missing a cover to prevent water from entering an enclosure.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J01 I
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: a) Historic House Basement; Five florescent light fixtures were located 6 feet 10 inches from the floor and were not guarded to prevent accidental breakage/contact.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07 I
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.
Recent events (2)
- — I (S) $0
- — Z (R) $0
1910.303 B02
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.
Recent events (2)
- — I (S) $0
- — Z (R) $0
1910.101 B
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: a) Office L-103; Compressed breathing air gas cylinders were stored unsecured adjacent to a deck.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 E02
- Issued
- Sep 9, 2016
- Abate by
- Oct 14, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) Baker Lab; The Amerex fire extinguisher adjacent to the refrigerator was not visually inspected at least monthly. b) Baker Lab; The kiddie fire extinguisher by the door was not visually inspected at least monthly. c) Olympus Lab; The Amerex fire extinguisher by the door was not visually inspected at least monthly. d) Rainier Lab; The Amerex fire extinguisher by the sink was not visually inspected at least monthly. e) Pump House; The Amerex fire extinguisher was not visually inspected at least monthly. f) Laboratory Room L108; The American LaFrance fire extinguisher was not visually inspected at least monthly.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at U.S. Geological Survey, Wfrc Marrowstone Marine Field Station
View U.S. Geological Survey, Wfrc Marrowstone Marine Field Station's full OSHA safety record →
More inspections in this industry (NAICS 541710)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341681351.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.