Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: STRATFORD STEEL, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of STRATFORD STEEL, LLC in 185 MASARIK AVENUE, STRATFORD, CT 06615 (NAICS 332312). OSHA activity number 341692275.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Stratford Steel, LLC — free Get an email when a new federal OSHA severe-injury report for Stratford Steel, LLC is published. One employer, no account, unsubscribe in one click.
Site address
185 MASARIK AVENUE
City
STRATFORD
State
CT
ZIP
06615
Mailing
185 MASARIK AVENUE, STRATFORD, CT 06615
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
19
Ownership type
A

10 citations on file for this inspection.

1910.178 L03 I M

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 18, 2016
Abate by
Dec 15, 2016
Penalty
Initial $6,236 · Current $3,860 Reduced
29 CFR 1910.178(l)(3)(i)(M): Powered industrial truck operators did not receive initial training in the following topics to include but not limited to operating instructions, warnings, or precautions listed in the operator's manual for the types of vehicle that the employee was being trained to operate:    ESTABLISHMENT:  The operator, required to operate the Hyster H40J forklift was not provided with information and training specific to the type forklift prior to operating the forklift truck.
Recent events (2)
  • — I (S) $3860
  • — Z (S) $6236

1910.178 P01

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 18, 2016
Abate by
Dec 1, 2016
Penalty
Initial $6,236 · Current $3,860 Reduced
29 CFR 1910.178(p)(1): Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been  taken out of service until restored to safe operating condition(s):    ESTABLISHMENT:  The Hyster H40J forklift did not have an active horn, was missing a light, a split tire, and was not removed from service until it was in safe operating condition.
Recent events (2)
  • — I (S) $3860
  • — Z (S) $6236

1910.303 F02

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 18, 2016
Abate by
Dec 1, 2016
Penalty
Initial $6,236 · Current $3,860 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    ESTABLISHMENT:  Each circuit breaker located in Electrical Panel #2 was not legibly marked to indicate its purpose.
Recent events (2)
  • — I (S) $3860
  • — Z (S) $6236

1910.305 A02 X

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 18, 2016
Abate by
Dec 1, 2016
Penalty
Initial $6,236 · Current $3,860 Reduced
29 CFR 1910.305(a)(2)(x): Flexible cords were not protected from accidental damage, as might be caused for example, by sharp corners, projections, and doorways or other pinch points:    ESTABLISHMENT:  The orange flexible cord used to power a Milwaukee Deep cut Band Saw was subject to damage where it went around a wooden wall and under the open doors of a supply cabinet.
Recent events (2)
  • — I (S) $3860
  • — Z (S) $6236

1910.305 B01 II

Serious Gravity 5 2 instances 2 exposed
Issued
Nov 18, 2016
Abate by
Dec 1, 2016
Penalty
Initial $6,236 · Current $3,860 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes and fittings were not effectively closed:    ESTABLISHMENT:     1. Marvel Series V10 A saw control panel had an unused opening.    2. There was one unused opening in Electrical Panel #2.
Recent events (2)
  • — I (S) $3860
  • — Z (S) $6236

1910.305 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 18, 2016
Abate by
Dec 1, 2016
Penalty
Initial $6,236 · Current $3,860 Reduced
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    ESTABLISHMENT:  The duplex electrical outlet box used to power a Milwaukee Deep Cut band saw, was not equipped with a faceplate.
Recent events (2)
  • — I (S) $3860
  • — Z (S) $6236

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 18, 2016
Abate by
Dec 1, 2016
Penalty
Initial $6,236 · Current $3,860 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    ESTABLISHMENT:  The outer sheathing of the nonmetallic flexible cord was separated from the attachment plug of a Lincoln Power Mig 255.
Recent events (2)
  • — I (S) $3860
  • — Z (S) $6236

1910.1200 E01

Repeat Gravity 5 1 instance 4 exposed
Issued
Nov 18, 2016
Abate by
Dec 15, 2016
Penalty
Initial $9,976 · Current $5,980 Reduced
29 CFR 1910.1200(e)(1): Employer had not developed or implemented a written hazard communication program included the requirements outlined in 29 CFR 1910.1200(e)(1)(i) and (e)(1)(ii):    ESTABLISHMENT: The employer did not develop or implement a written Hazard Communication program where employees were required to work with and/or handle hazardous chemicals, such as (but not limited to) propane and welding gases.    STRATFORD STEEL LLC was previously cited for a violation of this Occupational Safety and Health standard {29 CFR 1910.1200(e)(1)}, which was contained in OSHA Inspection Number 1137766, Citation Number 01, Item Number 005a and was affirmed as a final order on 04/22/2016, with respect to a workplace located at 185 Masarik Avenue, Stratford, CT 06615.
Recent events (2)
  • — I (R) $5980
  • — Z (R) $9976

1910.101 B

Other-than-serious 1 instance 1 exposed
Issued
Nov 18, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  ESTABLISHMENT:  The Argon compressed gas cylinder in storage was subject to damage while stored near an electrical outlet without being secured to prevent the cylinder from falling.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 F01

Other-than-serious 1 instance 2 exposed
Issued
Nov 18, 2016
Abate by
Dec 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(f)(1): All conductors used for general wiring were not insulated unless otherwise permitted in this subpart.  ESTABLISHMENT:    1. The outer insulation of an orange flexible cord used to power Miller Wire feeder machine had multiple rips exposing inner insulated conductors.  2. A piece of outer insulation was missing from a flexible cord used to power a Lincoln Power Mig 255.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Stratford Steel, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341692275.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.