Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LMN DEVELOPMENT, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of LMN DEVELOPMENT, LLC in 7000 KALAHARI DRIVE, SANDUSKY, OH 44870 (NAICS 531120). OSHA activity number 341706562.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch LMN Development, LLC — free Get an email when a new federal OSHA severe-injury report for LMN Development, LLC is published. One employer, no account, unsubscribe in one click.
Site address
7000 KALAHARI DRIVE
City
SANDUSKY
State
OH
ZIP
44870
Mailing
7000 KALAHARI DRIVE, SANDUSKY, OH 44870
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
531120
Employees
1300
Ownership type
A

5 citations on file for this inspection.

1910.332 B01

Serious Gravity 10 1 instance 4 exposed
Issued
Nov 15, 2016
Abate by
Dec 30, 2016
Penalty
Initial $12,471 · Current $6,235 Reduced

Hazardous substances 8870

29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments.    a. LMN Development, LLC located in Sandusky, Ohio:  On or about July 2, 2016, the employer did not ensure employees performing electrical work and exposed to electrical hazards were properly trained on the following topics:        1. How to properly lockout electrical systems and to verify the deenergization of electrical systems;    2. How to inspect electrical protective equipment;    3. What personal protective equipment needs to be worn when performing electrical work;    4. Proper use and inspection of electrical testing equipment;    5. Electrical shock and arc blast/flash hazards;
Recent events (2)
  • — I (S) $6235
  • — Z (S) $12471

1910.333 A

Serious Gravity 10 2 instances 4 exposed
Issued
Nov 15, 2016
Abate by
Dec 30, 2016
Penalty
Initial $12,471 · Current $6,230 Reduced

Hazardous substances 8870

29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were  or could have been energized. The specific safety-related work practices were not consistent with the nature and extent of the associated electrical hazards.    a. LMN Development, LLC located in Sandusky, Ohio:  On or about July 2, 2016, the employer did not ensure an employee rewiring a 110 volt light switch, deenergized the electrical energy to the switch prior to performing work.  The employee received a severe electrical shock which required him to seek medical treatment.    b. LMN Development, LLC located in Sandusky, Ohio:  On or about August 15, 2016, the employer did not ensure an employee working inside of the 480 volt electrical panel SP-3B in Building B North, deenergized the electrical panel prior to performing work inside of the panel.  The employee received a severe electrical shock which required him to seek medical treatment.
Recent events (2)
  • — I (S) $6230
  • — Z (S) $12471

1910.333 B02 I

Serious Gravity 10 1 instance 4 exposed
Issued
Nov 15, 2016
Abate by
Dec 30, 2016
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives.    a. LMN Development, LLC located in Sandusky, Ohio:  On or about July 2, 2016, the employer did not ensure electrical system lockout procedures were developed which covered operations such as but not limited to employees working inside of the 480 volt electrical panels to troubleshoot fuses and employees rewiring new light switches inside of guest rooms.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 II B

Serious Gravity 10 2 instances 4 exposed
Issued
Nov 15, 2016
Abate by
Dec 30, 2016
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on was not disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures.    a. LMN Development, LLC located in Sandusky, Ohio:  On or about July 2, 2016, the employer did not ensure an employee rewiring a 110 volt light switch, deenergized the electrical energy to the switch prior to performing work.  The employee received a severe electrical shock which required him to seek medical treatment.    b. LMN Development, LLC located in Sandusky, Ohio:  On or about August 15, 2016, the employer did not ensure an employee working inside of the 480 volt electrical panel SP-3B in Building B North, deenergized the electrical panel prior to performing work inside of the panel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 2 instances 4 exposed
Issued
Nov 15, 2016
Abate by
Dec 30, 2016
Penalty
Initial $12,471 · Current $6,235 Reduced

Hazardous substances 8870

29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed.     a. LMN Development, LLC located in Sandusky, Ohio:  On or about July 2, 2016, the employer did not ensure employees performing electrical work and exposed to electrical hazards used protective equipment for the hands when rewiring a 110 volt light switch.     b. LMN Development, LLC located in Sandusky, Ohio:  On or about August 15, 2016, the employer did not ensure employees performing electrical work and exposed to electrical hazards used protective clothing for the upper body, lower body, face, head, and hands when troubleshooting a 480 volt fuses inside of electrical panel SP-3B located in Building B North.
Recent events (2)
  • — I (S) $6235
  • — Z (S) $12471

View LMN Development, LLC's full OSHA safety record →