SANDUSKY, OH —
OSHA Inspection: LMN DEVELOPMENT, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of LMN DEVELOPMENT, LLC in 7000 KALAHARI DRIVE, SANDUSKY, OH 44870 (NAICS 531120). OSHA activity number 341706562.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LMN DEVELOPMENT, LLC
- Site address
- 7000 KALAHARI DRIVE
- City
- SANDUSKY
- State
- OH
- ZIP
- 44870
- Mailing
- 7000 KALAHARI DRIVE, SANDUSKY, OH 44870
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 531120
- Employees
- 1300
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.332 B01
- Issued
- Nov 15, 2016
- Abate by
- Dec 30, 2016
- Penalty
- Initial $12,471 · Current $6,235 Reduced
8870
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments. a. LMN Development, LLC located in Sandusky, Ohio: On or about July 2, 2016, the employer did not ensure employees performing electrical work and exposed to electrical hazards were properly trained on the following topics: 1. How to properly lockout electrical systems and to verify the deenergization of electrical systems; 2. How to inspect electrical protective equipment; 3. What personal protective equipment needs to be worn when performing electrical work; 4. Proper use and inspection of electrical testing equipment; 5. Electrical shock and arc blast/flash hazards;
Recent events (2)
- — I (S) $6235
- — Z (S) $12471
1910.333 A
- Issued
- Nov 15, 2016
- Abate by
- Dec 30, 2016
- Penalty
- Initial $12,471 · Current $6,230 Reduced
8870
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could have been energized. The specific safety-related work practices were not consistent with the nature and extent of the associated electrical hazards. a. LMN Development, LLC located in Sandusky, Ohio: On or about July 2, 2016, the employer did not ensure an employee rewiring a 110 volt light switch, deenergized the electrical energy to the switch prior to performing work. The employee received a severe electrical shock which required him to seek medical treatment. b. LMN Development, LLC located in Sandusky, Ohio: On or about August 15, 2016, the employer did not ensure an employee working inside of the 480 volt electrical panel SP-3B in Building B North, deenergized the electrical panel prior to performing work inside of the panel. The employee received a severe electrical shock which required him to seek medical treatment.
Recent events (2)
- — I (S) $6230
- — Z (S) $12471
1910.333 B02 I
- Issued
- Nov 15, 2016
- Abate by
- Dec 30, 2016
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives. a. LMN Development, LLC located in Sandusky, Ohio: On or about July 2, 2016, the employer did not ensure electrical system lockout procedures were developed which covered operations such as but not limited to employees working inside of the 480 volt electrical panels to troubleshoot fuses and employees rewiring new light switches inside of guest rooms.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 B02 II B
- Issued
- Nov 15, 2016
- Abate by
- Dec 30, 2016
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on was not disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures. a. LMN Development, LLC located in Sandusky, Ohio: On or about July 2, 2016, the employer did not ensure an employee rewiring a 110 volt light switch, deenergized the electrical energy to the switch prior to performing work. The employee received a severe electrical shock which required him to seek medical treatment. b. LMN Development, LLC located in Sandusky, Ohio: On or about August 15, 2016, the employer did not ensure an employee working inside of the 480 volt electrical panel SP-3B in Building B North, deenergized the electrical panel prior to performing work inside of the panel.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Nov 15, 2016
- Abate by
- Dec 30, 2016
- Penalty
- Initial $12,471 · Current $6,235 Reduced
8870
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed. a. LMN Development, LLC located in Sandusky, Ohio: On or about July 2, 2016, the employer did not ensure employees performing electrical work and exposed to electrical hazards used protective equipment for the hands when rewiring a 110 volt light switch. b. LMN Development, LLC located in Sandusky, Ohio: On or about August 15, 2016, the employer did not ensure employees performing electrical work and exposed to electrical hazards used protective clothing for the upper body, lower body, face, head, and hands when troubleshooting a 480 volt fuses inside of electrical panel SP-3B located in Building B North.
Recent events (2)
- — I (S) $6235
- — Z (S) $12471
More inspections at LMN Development, LLC
View LMN Development, LLC's full OSHA safety record →
More inspections in this industry (NAICS 531120)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341706562.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.