OSHA Inspection: NEWPORT HOSPITAL

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NEWPORT HOSPITAL in 11 FRIENDSHIP STREET, NEWPORT, RI 02840 (NAICS 622110). OSHA activity number 341713139.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Newport Hospital — free Get an email when a new federal OSHA severe-injury report for Newport Hospital is published. One employer, no account, unsubscribe in one click.
Establishment
NEWPORT HOSPITAL
Site address
11 FRIENDSHIP STREET
City
NEWPORT
State
RI
ZIP
02840
Mailing
11 FRIENDSHIP STREET, NEWPORT, RI 02840
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
850
Ownership type
A

5 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 10 1 instance 16 exposed
Issued
Dec 12, 2016
Abate by
Apr 25, 2017
Penalty
Initial $12,471 · Current $8,730 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:    Establishment: On, or about, 08/12/2016 the employer did not develop and implement machine specific procedures to control hazardous energy during maintenance and servicing of equipment in the following instances:    (a)  Rooftop: Procedures were not developed, documented and utilized for the control of potentially hazardous energy for the HVAC units.    (b)  Facility: Procedures were not developed, documented and utilized for the control of potentially hazardous energy for the Industrial pump units.
Recent events (2)
  • — I (S) $8730
  • — Z (S) $12471

1910.147 C06 I

Serious Gravity 5 1 instance 16 exposed
Issued
Dec 12, 2016
Abate by
Apr 25, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  Establishment: On, or about, 08/12/2016 the employer did not perform a periodic inspection at least annually of the Energy Control Program whereby several years had passed since the last inspection of the procedures.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 F02

Serious Gravity 10 1 instance 16 exposed
Issued
Dec 12, 2016
Abate by
Mar 1, 2017
Penalty
Initial $12,471 · Current $8,730 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    Turner Building Closet 107: On, or about, 08/12/2016 the employer did not ensure that electric cabinets L1B and EML1B were legibly marked to indicate the purpose of each circuit.
Recent events (2)
  • — I (S) $8730
  • — Z (S) $12471

1910.333 A01

Serious Gravity 5 1 instance 16 exposed
Issued
Dec 12, 2016
Abate by
Jan 30, 2017
Penalty
Initial $7,572 · Current $5,300 Reduced
29 CFR 1910.333(a)(1): The employer failed to ensure that live parts were deenergized before employees began to work on or near live parts.    Establishment: On, or about, 08/12/2016 the employer did not ensure that live parts were deenergized before employees performed work on light ballasts.
Recent events (2)
  • — I (S) $5300
  • — Z (S) $7572

1910.333 B02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 12, 2016
Abate by
Mar 14, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:  Establishment: On, or about, 08/12/2016 the employer did not develop, document, and maintain written procedures for the control of potentially hazardous electrical energy during maintenance and servicing.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Newport Hospital's full OSHA safety record →