Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SAM-SON LOGISTICS INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SAM-SON LOGISTICS INC in 203 EGGERT ROAD, BUFFALO, NY 14215 (NAICS 484121). OSHA activity number 341725240.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sam-Son Logistics INC — free Get an email when a new federal OSHA severe-injury report for Sam-Son Logistics INC is published. One employer, no account, unsubscribe in one click.
Site address
203 EGGERT ROAD
City
BUFFALO
State
NY
ZIP
14215
Mailing
203 EGGERT ROAD, BUFFALO, NY 14215
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
484121
Employees
50
Ownership type
A

4 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Jan 5, 2017
Abate by
Feb 21, 2017
Penalty
Initial $3,741 · Current $2,200 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    a) On or about 8/16/16 at 203 Eggert Road, Buffalo, New York; in the southwest corner of the warehouse, a 120/240 volt panel for receptacle and lighting circuits did not have a cover.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $2200
  • — Z (S) $3741

1910.334 A02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Jan 5, 2017
Abate by
Feb 21, 2017
Penalty
Initial $3,741 · Current $2,200 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):    a) On or about 8/16/16 at 203 Eggert Road, Buffalo, New York; in the warehouse, extension cords were being used to provide power to fans and pumps. The cords had the molded end pulled away from jacket exposing the conductors.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $2200
  • — Z (S) $3741

1910.303 B02

Other-than-serious 1 instance 22 exposed
Issued
Jan 5, 2017
Abate by
Feb 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  a) On or about 8/16/16 at 203 Eggert Road, Buffalo, New York; in the warehouse, re-locatable power taps (power strips) were being used to provide power to various appliances and chargers. Re-locatable power taps are listed for household use and are not approved for commercial or industrial environments.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 22 exposed
Issued
Jan 5, 2017
Abate by
Feb 21, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) On or about 8/16/16 at 203 Eggert Road, Buffalo, New York; throughout the warehouse, extension cords were used in place of permanent wiring to provide power to items such as, but not limited to, pumps, fans and work stations.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341725240.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.