Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HANNAFORD BROS. CO., LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HANNAFORD BROS. CO., LLC in 8 MARKET STREET, WEST LEBANON, NH 03784 (NAICS 445110). OSHA activity number 341737682.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hannaford Bros. CO., LLC — free Get an email when a new federal OSHA severe-injury report for Hannaford Bros. CO., LLC is published. One employer, no account, unsubscribe in one click.
Site address
8 MARKET STREET
City
WEST LEBANON
State
NH
ZIP
03784
Mailing
145 PLEASANT HILL RD, SCARBOROUGH, ME 04074
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
445110
Employees
140
Ownership type
A

2 citations on file for this inspection.

1910.303 B08 III

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 2, 2016
Abate by
Dec 8, 2016
Penalty
Initial $8,908 · Current $8,908
29 CFR 1910.303(b)(8)(iii): Electric equipment provided with ventilating openings was installed so that walls or other obstructions prevent the free circulation of air through the equipment:  a. Compressor Room- Employees are not protected from a fire hazard where two Square D 480 volt step down transformers with ventilation openings had combustible materials stored behind, in front, and on top of the equipment preventing the full amount of air flow to go through the equipment for cooling purposes and additionally providing a fuel source for a fire.
Recent events (2)
  • — I (S) $8908
  • — Z (S) $8908

1910.303 G01 II

Other-than-serious 2 instances 50 exposed
Issued
Dec 2, 2016
Abate by
Dec 8, 2016
Penalty
Initial $8,908 · Current $0 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    a. Stock Room- Employees were not protected from electric shock, fire, and trip hazards where the electric disconnect for the forklift battery charger, the forklift battery charger, and the electric disconnects for the compressors were blocked by stored merchandise and materials.    b. Stock Room and Compressor Room- Electrical panel boards had stored merchandise and materials within their required working space.