Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: KINDER MORGAN PRODUCTION CO., INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of KINDER MORGAN PRODUCTION CO., INC. in 1800 HWY 190 WEST, IRAAN, TX 79744 (NAICS 221210). OSHA activity number 341776136.

Watch Kinder Morgan Production CO., INC. — free Get an email when a new federal OSHA severe-injury report for Kinder Morgan Production CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
1800 HWY 190 WEST
City
IRAAN
State
TX
ZIP
79744
Mailing
1800 HWY 190 WEST, IRAAN, TX 79744
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
Yes
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221210
Employees
100
Ownership type
A

4 citations on file for this inspection.

1910.333 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $8465.00 · Current $6000.00 Reduced
29 CFR 1910.333(a)(1): Live parts that the employee was exposed to were not de-energized before the work began in or near them.      On September 14, 2016, an employee was inspecting an electrical cabinet, where there were exposed electrical busses, without first assuring the electrical cabinet was de-energized. The employee was exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $6000
  • — Z (S) $8465

1910.333 B02 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2)(iv): Qualified persons did not use test equipment to test the circuit elements and electrical parts of equipment to which employees were exposed and verify the circuit elements and equipment parts were de-energized.    On or about September 14, 2016, employees were troubleshooting an electrical system which had experienced a power outage without first verifying electrical power source was de-energized.  Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 I

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $8465.00 · Current $4200.00 Reduced
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) and did not make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives.    On September 14, 2016, the employer did not have complete written procedures as outlined in paragraph (b)(2) of 29 CFR 1910.333 for inspection by OSHA.
Recent events (2)
  • — I (O) $4200
  • — Z (S) $8465

1910.335 A01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $8465.00 · Current $6000.00 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards did not use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.     On or about September 14, 2016, employees were not provided with gloves to protect the hands in the event contact was made with live electrical parts.  Employees were exposed to electrical shock hazards.