LEMOORE, CA ·
OSHA Inspection: NAS LEMOORE -NAVFAC PWD
Other inspection · Safety discipline
At a glance
On , OSHA opened an other safety inspection of NAS LEMOORE -NAVFAC PWD in NAVFAC 750 ENTERPRISE AVE, LEMOORE, CA 93246 (NAICS 928110). OSHA activity number 341788388.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NAS LEMOORE -NAVFAC PWD
- Site address
- NAVFAC 750 ENTERPRISE AVE
- City
- LEMOORE
- State
- CA
- ZIP
- 93246
- Mailing
- NAVFAC 750 ENTERPRISE AVE, LEMOORE, CA 93246
What kind of inspection was it?
- Inspection type
- Other (L)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 183
- Ownership type
- Federal government (D)
Citations
6 citations on file for this inspection.
1910.147 C04 II
- Issued
- Sep 30, 2016
- Abate by
- Dec 15, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(ii): The energy control procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, items A-D of this section: a) NAS Lemoore, NAVFAC Public Works Department (PWD): On or about June 15, 2016, the NAVFAC PWD Lockout/Tagout (LOTO) procedure failed to specify procedural steps for the placement for the placement, removal, and transfer of LOTO devices and the responsibility for them while work was conducted on Padmounted Switchgears. An employee suffered second and third degree burns after receiving an electric shock from the 12kv electrical system while attempting to replace the Padmounted Switchgear.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.147 C06 I
- Issued
- Sep 30, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed: a) NAS Lemoore, NAVFAC Public Works Department (PWD): On or about June 15, 2016, NAVFAC PWD did not conduct a periodic (at least annual) inspection of its energy control procedure to ensure that the procedure and the requirements of the LOTO standard were being followed. The latest inspection was completed April 15, 2015. An employee was exposed to an electric shock from 12kv electrical system which resulted in second and third degree burns.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.147 C07 III A
- Issued
- Sep 30, 2016
- Abate by
- Dec 15, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(iii)(A): Retraining was not provided for all authorized and affected employees whenever there was a change in their job assignments, a change in machines, equipment or processes that present a new hazard, or when there was a change in the energy control procedures: a) NAS Lemoore, NAVFAC Public Works Department (PWD): On or about June 15, 2016, NAVFAC PWD did not provide retraining for high voltage electricians. An employee was exposed to an electric shock from 12kv electrical system which resulted in second and third degree burns.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.147 D05 II
- Issued
- Sep 30, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(d)(5)(ii): If there was a possibility of reaccumulation of stored energy to a hazardous level, verification of isolation did not continue until the servicing or maintenance was completed, or until the possibility of such accumulation no longer existed. a) NAS Lemoore, NAVFAC Public Works Department (PWD): On or about June 15, 2016, NAVFAC PWD did not take appropriate measures to retest or re-verify to prevent re-accumulation of electrical voltage up to 12kv. An employee was exposed to an electric shock from 12kv electrical system which resulted in second and third degree burns.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.335 A01 I
- Issued
- Sep 30, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards shall be provided with, and shall use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed. Note: Personal protective equipment requirements are contained in subpart I of this part. a) NAS Lemoore, NAVFAC Public Works Department (PWD): On or about June 15, 2016, NAVFAC PWD did not require an electrician to wear appropriate high voltage gloves to clean and apply silicone to 600 amp T-Body elbow connection with cotton material. An employee was exposed to an electrical shock from 12kv electrical system which resulted in second and third degree burns.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.335 A02 I
- Issued
- Sep 30, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment if the tools or handling equipment might make contact with such conductors or parts. If the insulating capability of insulated tools or handling equipment was subject to damage, the insulating material shall be protected. a) NAS Lemoore, NAVFAC Public Works Department (PWD): On or about June 15, 2016, NAVFAC PWD did not require to use an insulated tools to secure T-Bodies to bushings inside the Padmounted Switchgear. An employee was exposed to an electric shock from 12kv electrical system which resulted in second and third degree burns.