SYRACUSE, NY —
OSHA Inspection: AMERICOLD LOGISTICS LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of AMERICOLD LOGISTICS LLC in 264 FARRELL ROAD, SYRACUSE, NY 13209 (NAICS 493120). OSHA activity number 341788743.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMERICOLD LOGISTICS LLC
- Site address
- 264 FARRELL ROAD
- City
- SYRACUSE
- State
- NY
- ZIP
- 13209
- Mailing
- 264 FARRELL ROAD, SYRACUSE, NY 13209
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 30
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 D03 I B
- Issued
- Mar 14, 2017
- Abate by
- Mar 24, 2017
- Penalty
- Initial $7,243 · Current $4,312 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): Information pertaining to the equipment in the process did not include piping and instrumentation diagrams: a) On or about 9/21/2016, In the engine room: An unlabeled secondary valve and tee were attached to the system after vent valve V3, located near the high pressure receiver, just after the king valve, this was not denoted on the P&ID. Abatement certification is required for this item.
Recent events (3)
- — J (S) $4312
- — C (S) $7243
- — Z (S) $7243
1910.119 D03 II
- Issued
- Mar 14, 2017
- Abate by
- Mar 24, 2017
- Penalty
- Initial $7,243 · Current $4,311 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: a) On or about 9/21/2016, On the roof: The employer did not comply with recognized and generally accepted good engineering practices (RAGAGEP) such as IIAR 2 2012, section 5.14, when it did not label or mark process piping containing high pressure liquid ammonia, high pressure ammonia vapor and low pressure ammonia exposing employees to the hazard of contact with or inhalation of anhydrous ammonia. b) On or about 9/21/2016, In the engine room: The employer did not comply with recognized and generally accepted good engineering practices (RAGAGEP) such as IIAR 2 2012, section 5.14, when it did not label or mark process piping containing high pressure liquid ammonia, high pressure ammonia vapor and low pressure ammonia exposing employees to the hazard of contact with or inhalation of anhydrous ammonia. Abatement certification is required for this item.
Recent events (3)
- — J (S) $4311
- — C (S) $7243
- — Z (S) $7243
1910.119 D03 I D
- Issued
- Mar 14, 2017
- Abate by
- Mar 24, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): Information pertaining to the relief system design and design basis was not maintained: a) On or about 9/21/2016, On the roof: Information pertaining to the relief system design and design basis associated with the diffuser located at the terminus end of the emergency relief venting system was not available. Abatement certification is required for this item.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.119 J05
- Issued
- Mar 14, 2017
- Abate by
- Mar 24, 2017
- Penalty
- Initial $7,243 · Current $4,311 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) before use: a) On or about 9/21/2016, On the roof in AU6, AU13 and AU15: The employer did not correct deficiencies in process equipment where existing pipe hangers and supports had become disconnected from surrounding structures and piping, and were no longer supporting process piping. Abatement certification is required for this item.
Recent events (3)
- — J (S) $4311
- — C (S) $7243
- — Z (S) $7243
More inspections at Americold Logistics LLC
View Americold Logistics LLC's full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341788743.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.