MANSFIELD, PA —
OSHA Inspection: EUGENE HOUSE
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of EUGENE HOUSE in 1 LUTES AVENUE, MANSFIELD, PA 16933 (NAICS 321920). OSHA activity number 341790657.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EUGENE HOUSE
- Site address
- 1 LUTES AVENUE
- City
- MANSFIELD
- State
- PA
- ZIP
- 16933
- Mailing
- 1 LUTES AVENUE, MANSFIELD, PA 16933
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321920
- Employees
- 10
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C04 I
- Issued
- Oct 17, 2016
- Abate by
- Dec 5, 2016
- Penalty
- Initial $2,940 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees are engaged in the activities covered by this section: a) Mansfield, PA: Energy control procedures necessary to protect employees during blade changes and repairs on saws and other wood working machinery were not documented, on or about September 22, 2016 ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — C (S) $2940
- — F (S) $2000
- — Z (S) $2940
1910.147 D04 I
- Issued
- Oct 17, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(d)(4)(i): Lockout or tagout devices were not affixed to each energy isolating device by authorized employees: a) Production Area: Locks were not applied to power disconnects during blade changes and repairs on various wood cutting machines, on or about September 22, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.147 C07 I
- Issued
- Oct 17, 2016
- Abate by
- Dec 5, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program (lockout) was understood by employees: a) Mansfield, PA: Employees who routinely perform servicing and maintenance on wood cutting machinery have not received training on the purpose and function of the energy control (lockout) program, on or about September 22,2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.213 I01
- Issued
- Oct 17, 2016
- Abate by
- Dec 5, 2016
- Penalty
- Initial $2,940 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.213(i)(1): Non-working portion(s) of the blade of bandsaw(s) were not enclosed or guarded: a) Production Area: Guarding installed on the 54-inch McDonough band resaw did not adequately protect the operator and other workers from the unused portion of the blade, on or about September 22, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — C (S) $2940
- — F (S) $1000
- — Z (S) $2940
1910.332 B01
- Issued
- Oct 17, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $2,940 · Current $0 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): The employer does not train employees in safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) Production Area: An employee opened an energized 3-phase, 240 volt electrical panel box to check and replace a fuse without de-energizing the system or utilizing proper protective equipment, on or about September 22, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — C (S) $2940
- — F (S) $0
- — Z (S) $2940
1910.333 A01
- Issued
- Oct 17, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $0 · Current $2,000
General-duty citation text
29 CFR 1910.333(a)(1): The employer does not have live parts de-energized before each employee works on or near them: a) Production Area: An employee entered and replaced fuses in an energized 3-phase, 240 volt electrical panel box that had not been de-energized and locked out, on or about September 22, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — C (S) $0
- — F (S) $2000
- — Z (S) $0
1910.335 A01 I
- Issued
- Oct 17, 2016
- Abate by
- Oct 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): The employer does not provide employees working in areas where there are potential electrical hazards with electrical protective equipment that is appropriate for the specific parts of the body that need to be protected and for the work being performed: a) Production Area: An employee entered an energized 3-phase, 240 volt electrical panel box to replace a fuse without utilizing appropriate electrical protective equipment, on or about September 22, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.213 G01
- Issued
- Oct 17, 2016
- Abate by
- Jan 5, 2017
- Penalty
- Initial $5,879 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.213(g)(1): Swing cutoff saw(s) were not provided with an automatically adjusting hood that completely enclosed the upper half of the saw, the arbor end, and the point of operation at all positions of the saw: a) Production Area: The self adjusting guard on the swing arm saws had been fastened in the opened position exposing the operator to an amputation hazard, on or about September 22, 2016. ABATEMENT DOCUMENTATION AND CERTIFICATION REQUIRED House Wood Products was previously cited for a violation of this Occupational Safety and Health Administration standard or its equivalent standard, 29 CFR 1910.213(g)(1), which was contained in OSHA inspection number 1134026, citation number 1, item 2a, and was affirmed as a final order on June 10, 2016, with respect to a workplace located at 1 Lutes Avenue, Mansfield, PA.
Recent events (3)
- — C (R) $5879
- — F (S) $2000
- — Z (R) $5879
More inspections at Eugene House
View Eugene House's full OSHA safety record →
More inspections in this industry (NAICS 321920)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341790657.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.