Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ELK LIGHTING, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ELK LIGHTING, INC. in 40 3RD ST, WALNUTPORT, PA 18088 (NAICS 493110). OSHA activity number 341809754.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ELK Lighting, INC. — free Get an email when a new federal OSHA severe-injury report for ELK Lighting, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
ELK LIGHTING, INC.
Site address
40 3RD ST
City
WALNUTPORT
State
PA
ZIP
18088
Mailing
40 3RD ST, WALNUTPORT, PA 18088
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
130
Ownership type
A

3 citations on file for this inspection.

1910.305 B02 I

Serious Gravity 5 2 instances 35 exposed
Issued
Oct 18, 2016
Abate by
Oct 31, 2016
Penalty
Initial $5,451 · Current $5,451
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a)  Office - On or about October 5, 2016, the light switch was not provided with a cover to prevent employees coming into contact with the internal electrical wiring.   b)  Break Room - On or about October 5, 2016, electrical boxes on the ceiling and wall were not provided with a cover to prevent employees from coming into contact with internal wiring.
Recent events (1)
  • — Z (S) $5451

1910.305 G02 III

Serious 1 instance 5 exposed
Issued
Oct 18, 2016
Abate by
Oct 31, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  a)  Work Area - On or about October 5, 2016, the flexible cord powering the Global fan did not have installed strain relief at the plug.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Other-than-serious 1 instance 5 exposed
Issued
Oct 18, 2016
Abate by
Nov 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a)  Second Floor - On or about October 5, 2016, electrical knockout style boxes were not being used in accordance with its listing or label, as they were not attached to a permanent structure to prevent employees from coming into contact with internal live parts.
Recent events (1)
  • — Z (O) $0

View ELK Lighting, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341809754.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.