SELINSGROVE, PA —
OSHA Inspection: KERRICO CORPORATION
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of KERRICO CORPORATION in 2254 ROUTE 522, SELINSGROVE, PA 17870 (NAICS 327991). OSHA activity number 341810208.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KERRICO CORPORATION
- Site address
- 2254 ROUTE 522
- City
- SELINSGROVE
- State
- PA
- ZIP
- 17870
- Mailing
- 2254 ROUTE 522, SELINSGROVE, PA 17870
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327991
- Employees
- 18
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.107 G02
- Issued
- Jan 18, 2017
- Abate by
- Feb 22, 2017
- Penalty
- Initial $1,847 · Current $1,293 Reduced
2280
General-duty citation text
29 CFR 1910.107(g)(2): All spraying areas were not kept as free from the accumulation of deposits of combustible residues as practical, with cleaning conducted daily if necessary: a) Main spray booth, flammable liquids were sprayed and combustible overspray residue was built up on the booth walls, top panel, and floor, on or about, October 20, 2016. b) Small spray & speckle booth, flammable liquids were sprayed and combustible overspray residue was built up on the booth walls, top panel, and floor, on or about, October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1293
- — Z (S) $1847
1910.22 A01
- Issued
- Jan 18, 2017
- Abate by
- Feb 22, 2017
- Penalty
- Initial $0 · Current $0
2280
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition. a) Grinding booth, fine dust consisting of styrene resin and limestone was not removed from surfaces of nearby stored materials and the top of the booth and ventilation cabinets creating poor housekeeping, on or about, October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 E01
- Issued
- Jan 18, 2017
- Abate by
- Feb 22, 2017
- Penalty
- Initial $1,847 · Current $1,293 Reduced
General-duty citation text
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: a) An employee, Grinder, wore a negative pressure cartridge type half mask respirator during grinding and had not had a medical evaluation to determine if he could wear the respirator without adverse health effect, on or about, October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1293
- — Z (S) $1847
1910.134 F02
- Issued
- Jan 18, 2017
- Abate by
- Feb 22, 2017
- Penalty
- Initial $0 · Current $0
2280L100
General-duty citation text
29 CFR 1910.134(f)(2): Employee(s) using tight-fitting facepiece respirators were not fit tested prior to initial use of the respirator: a) An employee, Grinder, wore a negative pressure cartridge type half mask respirator during grinding and had not had a fit test to determine its effectiveness, on or about, October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 E01
- Issued
- Jan 18, 2017
- Abate by
- May 15, 2017
- Penalty
- Initial $2,463 · Current $1,721 Reduced
2280
General-duty citation text
29 CFR 1910.119(e)(1): The employer did not perform an initial process hazard analysis (hazard evaluation) on processes covered by 29 CFR 1910.119: a) A process hazard analysis was not developed for the hazard of normal rated electrical components in Class I Division II locations, within the resin tank dike; within the manual resin dispensing area; and in the area surrounding the interior resin holding tank and RESPECTA machine, on or about, October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1721
- — Z (S) $2463
1910.119 D03 I C
- Issued
- Jan 18, 2017
- Abate by
- May 15, 2017
- Penalty
- Initial $0 · Current $0
2280
General-duty citation text
29 CFR 1910.119(d)(3)(i)(C): Information pertaining to the equipment in the process did not include electrical classification: a) Classification of the electrical installations and components within the manual resin dispensing area; in the area surrounding the interior holding tank and RESPECTA machine, was not performed as evidenced by the presence of normal electrical equipment in Division II areas, on or about, October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F01 II A
- Issued
- Jan 18, 2017
- Abate by
- May 15, 2017
- Penalty
- Initial $1,847 · Current $1,293 Reduced
2280
General-duty citation text
29 CFR 1910.119(f)(1)(ii)(A): Written operating procedures were not developed and implemented that addressed consequences of deviation in each covered process: a) A written set of operating procedures for the resin storage, heating, plumbing and dispensing systems was not developed to include consequences of deviation, on or about October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1293
- — Z (S) $1847
1910.119 N
- Issued
- Jan 18, 2017
- Abate by
- Mar 24, 2017
- Penalty
- Initial $0 · Current $0
2280
General-duty citation text
29 CFR 1910.119(n): The employer did not establish an emergency plan for the entire plant in accordance with the provisions of 29 CFR 1910.38: a) A written emergency action plan was not developed and implemented which addressed the potential for resin spill and fire, on or about October 20, 2016. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Kerrico Corporation
View Kerrico Corporation's full OSHA safety record →
More inspections in this industry (NAICS 327991)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341810208.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.