NEW YORK, NY —
OSHA Inspection: HATZEL & BEUHLER INC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of HATZEL & BEUHLER INC in 388 GREENWICH ST, NEW YORK, NY 10013 (NAICS 238210). OSHA activity number 341837946.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HATZEL & BEUHLER INC
- Site address
- 388 GREENWICH ST
- City
- NEW YORK
- State
- NY
- ZIP
- 10013
- Mailing
- 3600 SILVERSIDE ROAD, WILMINGTON, DE 19810
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 3
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.20 B02
- Issued
- Apr 6, 2017
- Penalty
- Initial $9,054 · Current $9,000 Reduced
General-duty citation text
29 CFR 1926.20(b)(2): Such programs shall provide for frequent and regular inspections of the job sites, materials, and equipment to be made by competent persons designated by the employers. a) Employees were exposed to electric shock/ burns. The employer did not inspect of the work site where employees were going to work in an energized panel to ensure proper means and methods were followed. An arc flash occurred when the employee was working with the wiring in the panel. Location: 388 Greenwich St, New York, N.Y., 40th fl mechanical rm. On or about 10/08/2016 NOTE: BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASEFILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION NOR DOCUMENTATION OF ABATEMENT OF THIS ITEM IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (O) $9000
- — Z (S) $9054
1926.21 B02
- Issued
- Apr 6, 2017
- Penalty
- Initial $12,675 · Current $12,000 Reduced
General-duty citation text
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and regulatory requirements for controlling and eliminating hazards in the workplace: a) Employees were exposed to electric shock/ burns. Employees were not instructed on the means, methods and pre-task review to work on energized panels (480VAC) when connecting wiring in panels DPH-40B-2 and 40-B-4. An arc flash occurred when the employee was working in the panel. Location: 388 Greenwich St, New York, N.Y., 40th fl mechanical rm. On or about 10/08/2016 NOTE: BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASEFILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION NOR DOCUMENTATION OF ABATEMENT OF THIS ITEM IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (O) $12000
- — Z (S) $12675
1926.95 A
- Issued
- Apr 6, 2017
- Penalty
- Initial $12,675 · Current $12,000 Reduced
General-duty citation text
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided, used, and maintained in a sanitary and reliable condition wherever necessary by reason of hazards of processes or environment: a) Employees were working in an energized electric panel DPH-40B-2 and 40-B-4 without using personal protective equipment for the face, hands and body. An arc flash occurred causing an employee to be burned on his body. Location: 388 Greenwich St, New York, N.Y., 40th fl mechanical rm. On or about 10/08/2016 NOTE: BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASEFILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION NOR DOCUMENTATION OF ABATEMENT OF THIS ITEM IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (O) $12000
- — Z (S) $12675
1926.416 A01
- Issued
- Apr 6, 2017
- Penalty
- Initial $12,675 · Current $12,000 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): The employer did not ensure that: No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit during the course of work unless the employee is protected against electric shock by de-energizing the circuit and grounding it or by guarding it effectively by insulation or other means: a) Employees were exposed to electric shock/ burns. Employees were working in energized electric panels DPH-40B-2 and 40-B-4 and were not protected by using electrical PPE or insulating devices. Location: 388 Greenwich St, New York, N.Y. On or about 10/08/2016 NOTE: BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASEFILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION NOR DOCUMENTATION OF ABATEMENT OF THIS ITEM IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $12000
- — Z (S) $12675
1926.416 B01
- Issued
- Apr 6, 2017
- Penalty
- Initial $9,054 · Current $0 Reduced
General-duty citation text
29 CFR 1926.416(b)(1): The employer did not ensure that barriers or other means of guarding shall be provided to assure that work space for electrical equipment will not be used as a passageway during periods when energized parts of electric equipment are exposed: a) The employer did not have the aisle/work are barricaded to keep the passageway clear when energized electric panels DPH-40B-2 and 40-B-4 were being worked in. An arc flash occurred while work was being done in the energized panels. Location: 388 Greenwich St, New York, N.Y., 40th fl mechanical rm. On or about 10/08/2016 NOTE: BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASEFILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION NOR DOCUMENTATION OF ABATEMENT OF THIS ITEM IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $9054
More inspections at Hatzel & Beuhler INC