SAN JUAN, PR —
OSHA Inspection: U.S. CENTERS FOR DISEASE CONTROL AND PREVENTION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. CENTERS FOR DISEASE CONTROL AND PREVENTION in 1324 CA?ADA STREET, SAN JUAN, PR 00920 (NAICS 923120). OSHA activity number 341839561.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. CENTERS FOR DISEASE CONTROL AND PREVENTION
- Site address
- 1324 CA?ADA STREET
- City
- SAN JUAN
- State
- PR
- ZIP
- 00920
- Mailing
- 1324 CA?ADA STREET, SAN JUAN, PR 00920
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 923120
- Employees
- 120
- Ownership type
- D
Citations
2 citations on file for this inspection.
1910.304 B03 I
- Issued
- Mar 29, 2017
- Abate by
- Apr 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel: a) On or about 10/14/2016, Administrative building- room A018- break room area: Electrical receptacles were not equipped with ground-fault circuit-interrupter protection. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Mar 29, 2017
- Abate by
- Apr 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure. a. On or about 10/14/2016, Administrative building- room A018- break room area: Employees were using a flexible cord (extension cord) attached to an outlet box used to energize kitchen equipment. NOTE: Documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(d).
Recent events (1)
- — Z (S) $0
More inspections at U.S. Centers for Disease Control and Prevention
View U.S. Centers for Disease Control and Prevention's full OSHA safety record →
More inspections in this industry (NAICS 923120)
More inspections in PR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341839561.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.