LINCOLN, IL —
OSHA Inspection: WADDELL, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of WADDELL, INC. in 1709 N. KICKAPOO ST., LINCOLN, IL 62656 (NAICS 454390). OSHA activity number 341873503.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WADDELL, INC.
- Site address
- 1709 N. KICKAPOO ST.
- City
- LINCOLN
- State
- IL
- ZIP
- 62656
- Mailing
- 1709 N. KICKAPOO ST., LINCOLN, IL 62656
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 454390
- Employees
- 50
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.23 A08
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $4,988 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.23(a)(8): Every floor hole into which persons can accidentally walk were not guarded: On or about October 28, 2016, employees were exposed to fall hazards: a) in the Water Softener Area and the floor drain grates were missing on the trench drain; b) on top of the Clean Room and there were holes and areas of deterioration from water damage to the wood decking.
Recent events (2)
- — I (S) $3500
- — Z (S) $4988
1910.37 A04
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $3,741 · Current $0 Reduced
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: On or about November 2, 2016, employees were exposed to burn and smoke inhalation injuries and the emergency "Exit" illuminated signage was not operational at the East exit door of the Middle/Barn Area.
Recent events (2)
- — I (O) $0
- — Z (S) $3741
1910.37 B01
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that an employee with normal vision can see along the exit route. On or about November 2, 2016, emergency exit route lighting was not available at the West end of the Middle / Barn Area to ensure adequate emergency exit lighting during warehouse hours when natural lighting cannot be used to meet minimal lighting requirements.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.151 C
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $4,988 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.151(c): Where the eyes of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes were not available for immediate emergency use. On or about October 28, 2016, employees in the Middle Area/Barn exchanged 55-gallon drums of corrosive sodium hypochlorite solution (12.5-Percent; pH>10) that is used to treat the well water and the employer did not provide suitable facilities for quick drenching or flushing of the eyes for immediate emergency use.
Recent events (2)
- — I (S) $3500
- — Z (S) $4988
1910.303 B01 II
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $4,988 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided: On or about October 28, 2016, employees were exposed to electrical shock and burn hazards from wire raceways that are not glued to ensure mechanical continuity for the following equipment: a) wall mounted fan at the Northeast side of the Production Area. b) wall mounted fan at the Southeast side of the Production Area. c) wall mounted fan at the East side of the Middle Area/Barn. e) wall mounted fan at the West side of the Middle Area/Barn.
Recent events (2)
- — I (S) $3500
- — Z (S) $4988
1910.303 B02
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. On or about October 28, 2016, employees were exposed to electrical hazards and the employer did not install the following according to approved means: a) grey liquid tight flexible conduit that powered the East exit sign of the Middle Area/Barn secured to a water pipe with a piece of wire. b) drip proof box with a non-GFCI receptacle on the East wall of the DI Room that was installed below 3-inch Banjo valves that leak. c) plastic zip ties to secure grey liquid tight flexible conduit (between the control panel and softener tanks along the East wall of the DI Room) to a piece of metal channel. d) white PVC 90-degree elbows that are not approved for use as an electrical raceway serving the following: - Wall mounted fan at the Northeast side of the Production Area - Wall mounted fan at the Southeast side of the Production Area - Wall mounted fan at the East side of the Middle Area/Barn - Wall mounted fan at the West side of the Middle Area/Barn - Switch at the West side of the Middle Area/Barn
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07 IV
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electric equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. On or about October 28, 2016, employees in the DI Room were exposed to electrical shock and burn hazards from: a) a signal control panel in a water-tight type box suspended from Tank S2 and the box was cracked; b) a Square D electrical disconnect switch behind Tank S3 and the switch was inaccessible because it was stuck inside the enclosure; c) a Square D electrical disconnect switch behind Tank S3 and the enclosure was corroded by the purified water.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 E01 II
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Markings were not provided on electrical equipment for voltage, current, wattage and other ratings as necessary. On or about October 28, 2016, employees in the DI Room were exposed to electrical shock and burn hazards and the employer did not mark the Square D electrical disconnect switch (110V/20A) behind Tank 3 serving the brine tank with the voltage and current.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 F01 IV
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: On or about October 28, 2016, employees in the DI Room were exposed to electrical shock and burn hazards and the employer did not ensure sufficient access and working space between Tank 3 and the Square D electrical disconnect (110V/20A) serving the brine tank.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasions: On or about October 28, 2016, employees were exposed to electrical shock hazards in the DI Room and 110V insulated conductors were exposed to abrasion because the conductors were suspended between a Square D panel and a piece of grey non-metallic electrical conduit secured to a grey electrical condulet on the brine tank.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 II
- Issued
- Dec 1, 2016
- Abate by
- Jan 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap: On or about October 28, 2016, the employer provided the employees in the DI Room a signal control panel (110V) mounted inside a water-tight type enclosure and the unit's black flexible cord had been spliced and was held together with a wire nut and black tape.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Waddell, INC.
View Waddell, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 454390)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341873503.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.