OSHA Inspection: ARDENT MILLS, LLC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ARDENT MILLS, LLC. in 4200 SULLIVANT AVE., COLUMBUS, OH 43228 (NAICS 311211). OSHA activity number 341885010.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ardent Mills, LLC. — free Get an email when a new federal OSHA severe-injury report for Ardent Mills, LLC. is published. One employer, no account, unsubscribe in one click.
Establishment
ARDENT MILLS, LLC.
Site address
4200 SULLIVANT AVE.
City
COLUMBUS
State
OH
ZIP
43228
Mailing
4200 SULLIVANT AVE., COLUMBUS, OH 43228
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311211
Employees
24
Ownership type
A

5 citations on file for this inspection.

1910.333 B02 IV B

Other-than-serious 1 instance 8 exposed
Issued
Dec 20, 2016
Abate by
Sep 1, 2017
Penalty
Initial $9,799 · Current $5,879 Reduced
29 CFR 1910.333(b)(2)(iv)(B): A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately after this test.    a. Located at the mill: On or about November 2, 2016 and at times prior, the employer did not ensure that employees were using electrical testing equipment to verify that the hazardous energy was removed prior to replacing fuses and resetting internal motor overload devices at 480 volt motor control center units, exposing the employees to an arc flash and arc blast hazard.
Recent events (3)
  • — F (O) $5879.4
  • — C (S) $9799
  • — Z (S) $9799

1910.333 C02

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 20, 2016
Abate by
Sep 1, 2017
Penalty
Initial $9,799 · Current $5,879 Reduced
29 CFR 1910.333(c)(2): "Work on energized equipment." Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.    a. Located at the first floor of the Blend Plant: On or about October 12, 2016, an unqualified employee was instructed to reset the System B computer by opening up the panel cover and pulling out two eight amp, 120 volt, fuses. The employee did not wear electrical protective equipment and did not verify that the hazardous energy was removed prior to performing the work, exposing the employee to an electrical shock hazard.
Recent events (3)
  • — F (S) $5879.4
  • — C (S) $9799
  • — Z (S) $9799

1910.334 B02

Other-than-serious 1 instance 24 exposed
Issued
Dec 20, 2016
Abate by
Sep 1, 2017
Penalty
Initial $9,799 · Current $5,879 Reduced
29 CFR 1910.334(b)(2): Reclosing circuits after protective device operation. After a circuit is deenergized by a circuit protective device, the circuit may not be manually reenergized until it has been determined that the equipment and circuit can be safely energized. The repetitive manual reclosing of circuit breakers or reenergizing circuits through replaced fuses is prohibited.   Note: When it can be determined from the design of the circuit and the overcurrent devices involved that the automatic operation of a device was caused by an overload rather than a fault condition, no examination of the circuit or connected equipment is needed before the circuit is reenergized.    a. Located at the mill: On or about November 2, 2016 and at times prior, qualified employees were resetting motor overload devices and replacing fuses at 480 volt motor control center units. The employer did not ensure that employees determined that the equipment could safely be energized prior to reclosing the circuits, exposing employees to an arc flash hazard.
Recent events (3)
  • — F (O) $5879.4
  • — C (S) $9799
  • — Z (S) $9799

1910.335 A01 II

Other-than-serious 2 instances 8 exposed
Issued
Dec 20, 2016
Abate by
Sep 1, 2017
Penalty
Initial $13,718 · Current $0 Reduced
29 CFR 1910.335(a)(1)(ii): Protective equipment shall be maintained in a safe, reliable condition and shall be periodically inspected or tested, as required by 1910.137.    a. Located in room MCC 5 at the mill: On or about November 2, 2016 and at times prior, the employer did not ensure that the personal protective equipment used while performing electrical work inside the motor control center units was maintained in a safe and reliable condition which was free from damage and flour dust contamination, exposing employees to an arc flash and blast hazard.       b. Located in room MCC 2 at the mill: On or about November 2, 2016 and at times prior, the employer did not ensure that the personal protective equipment used while performing electrical work inside the motor control center units was maintained in a safe and reliable condition which was free from damage and flour dust contamination, exposing employees to an arc flash and blast hazard.
Recent events (3)
  • — F (O) $0
  • — C (S) $13718
  • — Z (S) $13718

1910.335 A01 I

Deleted Serious Gravity 5 1 instance 8 exposed
Issued
Dec 20, 2016
Abate by
Dec 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.  Note: Personal protective equipment requirements are contained in subpart I of this part.  a. On or about November 2, 2016 and at times prior, the employer did not ensure that employees exposed to arc blast hazards while replacing fuses and resetting motor starter overload devices in the motor control center units were provided with and utilized hearing protection.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0