OSHA Inspection: PUBLIC SERVICE COMPANY OF COLORADO

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PUBLIC SERVICE COMPANY OF COLORADO in N 38.31.1.22 W 104.41.4.26, FOUNTAIN, CO 80817 (NAICS 221112). OSHA activity number 341887545.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Public Service Company of Colorado — free Get an email when a new federal OSHA severe-injury report for Public Service Company of Colorado is published. One employer, no account, unsubscribe in one click.
Site address
N 38.31.1.22 W 104.41.4.26
City
FOUNTAIN
State
CO
ZIP
80817
Mailing
1800 LARIMER STREET #1100, DENVER, CO 80202
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
Employees
10
Ownership type
A

2 citations on file for this inspection.

1926.962 C

Serious Gravity 10 1 instance 10 exposed
Issued
Feb 17, 2017
Abate by
Jun 1, 2018
Penalty
Initial $12,675 · Current $12,675
29 CFR 1926.962(c): Temporary protective grounds were not placed at such locations and arranged in such a manner that the employer can demonstrate will prevent each employee from being exposed to hazardous differences in electric potential:      a) On or about October 20, 2016, and at times prior, workers were exposed to hazardous electrical energy when personal grounds were used in such a manner that a difference in potential was created between the East and West pole at location 331 (an H-Frame structure).          Note to paragraph (c): Appendix C to this subpart contains guidelines for establishing the equipotential zone required by this paragraph. The Occupational Safety and Health Administration will deem grounding practices meeting these guidelines as complying with paragraph (c) of this section.      Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $12675
  • — Z (S) $12675

1926.962 D01 I

Serious Gravity 5 1 instance 10 exposed
Issued
Feb 17, 2017
Abate by
Jun 1, 2018
Penalty
Initial $9,959 · Current $0 Reduced
29 CFR 1926.962(d)(1)(i): Protective grounding equipment was not capable of conducting the maximum fault current that could flow at the point of grounding for the time necessary to clear the fault:      a) On or about October 20, 2016, and at times prior, workers were exposed to hazardous electrical energy when three deenergized 320Kv conductors spanning approximately 50 miles from Comanche to Midway substations were grounded only through two #2 AWG copper conductors as the only replacement for substation grounds.      Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $9959