Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SC2 INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SC2 INC. in 6409 W. SMITHVILLE RD, BARTONVILLE, IL 61607 (NAICS 561910). OSHA activity number 341888550.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch SC2 INC. — free Get an email when a new federal OSHA severe-injury report for SC2 INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SC2 INC.
Site address
6409 W. SMITHVILLE RD
City
BARTONVILLE
State
IL
ZIP
61607
Mailing
6409 W. SMITHVILLE RD, BARTONVILLE, IL 61607
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561910
Employees
549
Ownership type
A

2 citations on file for this inspection.

1910.305 G01 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 6, 2017
Abate by
Jan 24, 2017
Penalty
Initial $7,126 · Current $4,988 Reduced
29 CFR 1910.305(g)(1)(iv)(A):  Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On or about November 3, 2016, employees were exposed to electrical and fire hazards near the aerial lift charging station when the electrical cord from the aerial lift was wired into an electrical box.
Recent events (2)
  • — I (S) $4988.2
  • — Z (S) $7126

1910.305 G01 IV D

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 6, 2017
Abate by
Jan 24, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and/or cables were attached to building surfaces:    On or about November 3, 2016, employees were exposed to electrical and fire hazards near the aerial lift charging station when a flexible cord used to charge batteries was zip tied to conduit attached to the wall.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View SC2 INC.'s full OSHA safety record →