MANCHESTER, CT —
OSHA Inspection: ITW GRAPHICS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ITW GRAPHICS in 375 NEW STATE ROAD, MANCHESTER, CT 06042 (NAICS 323113). OSHA activity number 341896389.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ITW GRAPHICS
- Site address
- 375 NEW STATE ROAD
- City
- MANCHESTER
- State
- CT
- ZIP
- 06042
- Mailing
- 375 NEW STATE ROAD, MANCHESTER, CT 06042
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323113
- Employees
- 100
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.106 E06 I
- Issued
- Dec 28, 2016
- Penalty
- Initial $4,543 · Current $3,180 Reduced
General-duty citation text
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors: Large Format Press: On, or about, November 7, 2016, potential ignition sources were located where ink was mixed on the Palmgren drill press. The drill press motor, a relocatable power tap and an electrical receptacle were located in the potential path of the vapors.
Recent events (2)
- — I (S) $3180.1
- — Z (S) $4543
1910.212 A01
- Issued
- Dec 28, 2016
- Penalty
- Initial $3,862 · Current $2,703 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: Inspection Area: On or about, November 7, 2016, the foot pedal control provided on the Dusenbery core cutting machine was not guarded to prevent accidental contact.
Recent events (2)
- — I (S) $2703.4
- — Z (S) $3862
1910.304 B04 II B
- Issued
- Dec 28, 2016
- Penalty
- Initial $3,862 · Current $2,703 Reduced
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4: Lab: On, or about, November 17, 2016, a Masterflow heat blower was energized through a 15 ampere Belkin relocatable power tap. The maximum load allowed on the device was 12 amperes and the blower was rated at 14 amperes.
Recent events (2)
- — I (S) $2703.4
- — Z (S) $3862
1910.305 G01 IV A
- Issued
- Dec 28, 2016
- Penalty
- Initial $5,149 · Current $3,604 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Sheet Feed Area: On, or about, November 7, 2016, an extension cord assembly was used to energize a mixing machine and a quality machine.
Recent events (2)
- — I (S) $3604.3
- — Z (S) $5149
1910.305 J02 I
- Issued
- Dec 28, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(i): Receptacles were not installed so that an energized attachment plug was not its source of supply: Inspection Area, Inspection Bench I15 and I11: A duplex receptacle used to energize two lights was energized through a cord and plug connection into another duplex receptacle mounted under an inspection bench.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.332 B01
- Issued
- Dec 28, 2016
- Abate by
- Feb 15, 2017
- Penalty
- Initial $7,572 · Current $5,300 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Plant-wide: On, or about, December 19, 2016, maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live trouble-shooting and while verifying whether or not electrical equipment was properly de-energized.
Recent events (2)
- — I (S) $5300.4
- — Z (S) $7572
1910.335 A01 I
- Issued
- Dec 28, 2016
- Abate by
- Feb 15, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Company: Personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 D04 I
- Issued
- Dec 28, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(4)(i): Openings to other rooms or buildings were not provided with approved self-closing fire doors: Flammable Storage Room: On, or about, November 7, 2016, fire doors that connected the flammable storage room to the small batch ink mixing room were routinely left open.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at ITW Graphics
View ITW Graphics's full OSHA safety record →
More inspections in this industry (NAICS 323113)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341896389.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.