CARROLLTON, OH —
OSHA Inspection: RAZOR EQUIPMENT SERVICES, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of RAZOR EQUIPMENT SERVICES, LLC in 3160 CANTON ROAD, CARROLLTON, OH 44615 (NAICS 532310). OSHA activity number 341931624.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RAZOR EQUIPMENT SERVICES, LLC
- Site address
- 3160 CANTON ROAD
- City
- CARROLLTON
- State
- OH
- ZIP
- 44615
- Mailing
- 3160 CANTON ROAD, CARROLLTON, OH 44615
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 532310
- Employees
- 20
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.333 C03 I A 2
- Issued
- Jan 10, 2017
- Abate by
- Jan 30, 2017
- Penalty
- Initial $4,988 · Current $3,492 Reduced
General-duty citation text
29 CFR 1910.333(c)(3)(i)(A): When an unqualified person is working in an elevated position near overhead lines, the location shall be such that the person and the longest conductive object he or she may contact cannot come closer to any unguarded, energized overhead line than the following distances: 29 CFR 1910.333(c)(3)(i)(A)(2): For voltages to ground over 50kV - 10 feet (305 cm) plus 4 inches (10 cm) for every 10kV over 50kV. a. On or before November 16, 2016, where an employee was operating an aerial lift near a 245 Kv electrical transmission line, a 20 foot minimum standoff distance was not maintained, resulting in an electrical arc from the lines to the aerial lift which caused burns and in-patient hospitalization of the employee.
Recent events (2)
- — I (O) $3491.6
- — Z (S) $4988
1910.335 B01
- Issued
- Jan 10, 2017
- Abate by
- Jan 30, 2017
- Penalty
- Initial $4,988 · Current $3,492 Reduced
General-duty citation text
29 CFR 1910.335(b)(1): Safety signs and tags. Safety signs, safety symbols, or accident prevention tags shall be used where necessary to warn employees about electrical hazards which may endanger them, as required by 1910.145. a. On or before November 16, 2016, where an employee was operating an aerial lift near a 245 Kv electrical transmission line, there were no signs warning employees about the hazards of the electrical transmission lines, thereby exposing employees to electrical contact hazards.
Recent events (2)
- — I (O) $3491.6
- — Z (S) $4988
More inspections in this industry (NAICS 532310)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341931624.