Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SEAPORT VILLAGE HEALTHCARE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SEAPORT VILLAGE HEALTHCARE in 19 GENERAL MOORE WAY, ELLSWORTH, ME 04605 (NAICS 623110). OSHA activity number 341953222.

Watch Seaport Village Healthcare — free Get an email when a new federal OSHA severe-injury report for Seaport Village Healthcare is published. One employer, no account, unsubscribe in one click.
Site address
19 GENERAL MOORE WAY
City
ELLSWORTH
State
ME
ZIP
04605
Mailing
19 GENERAL MOORE WAY, ELLSWORTH, ME 04605
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
95
Ownership type
A

5 citations on file for this inspection.

1910.212 A03 II

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $7126.00 · Current $7126.00
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):  Kitchen - The two kitchen garbage disposals were not guarded to prevent employees from having their hands in the blade area when attempting to clear jams.
Recent events (2)
  • — I (S) $7126
  • — Z (S) $7126

1910.303 B02

Serious Gravity 5 4 instances 7 exposed
Issued
Abate by
Penalty
Initial $8908.00 · Current $8908.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Kitchen and Electrical Room - Single pole breakers were wired together in lieu of double or triple pole breakers as required by the listing.
Recent events (2)
  • — I (S) $8908
  • — Z (S) $8908

1910.303 F

Serious Gravity 5 10 instances 95 exposed
Issued
Abate by
Penalty
Initial $10689.00 · Current $6236.00 Reduced
29 CFR 1910.303(f): Each disconnecting means for motors and appliances was not located and arranged so the purpose was evident, nor legibly marked to indicate its purpose:    Facility Wide - The electrical panels and circuit breakers in them were not labeled as to their purpose.
Recent events (2)
  • — I (S) $6236
  • — Z (S) $10689

1910.304 F01 IV

Serious Gravity 5 2 instances 6 exposed
Issued
Abate by
Penalty
Initial $8908.00 · Current $0.00 Reduced
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:    Main Kitchen - The two circuit breaker panels were locked and no key was available in case of an emergency.
Recent events (2)
  • — I (S) $0
  • — Z (S) $8908

1910.1030 G02 I

Other-than-serious 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $8908.00 · Current $0.00 Reduced
29 CFR 1910.1030(g)(2)(i): The employer did not ensure that each employee with occupational exposure participated in a training program:    Facility wide - Housekeeping and maintenance staff were not trained on the facilities procedures to control occupational exposure to blood or other potentially infectious materials.
Recent events (2)
  • — I (O) $0
  • — Z (S) $8908

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341953222.