OSHA Inspection: POWERTOWN LINE CONSTRUCTION LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of POWERTOWN LINE CONSTRUCTION LLC in 5700 27TH PLACE, NAPLES, FL 34117 (NAICS 238210). OSHA activity number 341956993.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Powertown Line Construction LLC — free Get an email when a new federal OSHA severe-injury report for Powertown Line Construction LLC is published. One employer, no account, unsubscribe in one click.
Site address
5700 27TH PLACE
City
NAPLES
State
FL
ZIP
34117
Mailing
11223 EAST US 92, SEFFNER, FL 33584
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
8
Ownership type
A

4 citations on file for this inspection.

1926.960 C01 III B

Serious Gravity 10 1 instance 1 exposed
Issued
May 30, 2017
Abate by
Jan 8, 2018
Penalty
Initial $11,408 · Current $5,704 Reduced
29 CFR 1926.960(c)(1)(iii)(B): The energized part was not insulated from the employee and from any other conductive object at a different potential:    On or about 12/7/2016, an employee received 2nd and 3rd degree burns from an arc flash while part of his upper right arm area made contact with an uninsulated area on "C" phase while his right hand was untying the insulator holding "B" phase resulting in a phase to ground arc flash due to a differences of potential.     PLEASE NOTE: DOCUMENTATION AND CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
  • — I (S) $5704
  • — Z (S) $11408

1926.960 C02 I B

Serious Gravity 10 1 instance 1 exposed
Issued
May 30, 2017
Abate by
Jan 8, 2018
Penalty
Initial $11,408 · Current $5,704 Reduced
29 CFR 1926.960(c)(2)(i)(B): When installing insulation for purposes of paragraph (c)(2)(i)(A) of this section, the employee installs the insulation from a position that does not expose his or her upper arm to contact with other energized parts:    On or about 12/7/2016, an employee installing line covers on conductors that were 13.2KV phase to ground and 23KV phase to phase was not wearing rubber sleeves when his upper right arm made contact with an uninsulated area on "C" phase while untying "B" phase from the insulator resulting in an arc flash.    PLEASE NOTE: DOCUMENTATION AND CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
  • — I (S) $5704
  • — Z (S) $11408

1926.960 D01

Serious Gravity 10 1 instance 1 exposed
Issued
May 30, 2017
Abate by
Jan 8, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.960(d)(1): Working from below. The employer did not ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, uninsulated parts energized at a potential different from the employee's:    On or about 12/7/2016, the employer did not ensure an employee worked in a position that would prevent him from his body making contact with uninsulated part on "C" phase, which had a break between the line hose that eventually caused an arc flash due to a differences of potential.    PLEASE NOTE: DOCUMENTATION AND CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.960 G02

Serious Gravity 10 1 instance 1 exposed
Issued
May 30, 2017
Abate by
Jan 8, 2018
Penalty
Initial $11,408 · Current $5,704 Reduced
29 CFR 1926.960(g)(2): For each employee exposed to hazards from electric arcs, the employer did not make a reasonable estimate of the incident heat energy to which the employee would be exposed:    On or about 12/7/2016, a foreman and qualified observer did not make a reasonable estimate of the incident heat energy when a lineman working on 13.2KV to 23 KV powerlines without rubber sleeves or face protection when the "C" phase was not fully covered with line hoses exposing a small break between the insulation and ultimately causing a phase to ground arc flash.     PLEASE NOTE: DOCUMENTATION AND CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
  • — I (S) $5704
  • — Z (S) $11408

View Powertown Line Construction LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341956993.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.