Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNITED STATES AIR FORCE 55 WING OFFUTT AIR FORCE BASE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of UNITED STATES AIR FORCE 55 WING OFFUTT AIR FORCE BASE in BUILDING 500 - STRATCOM, OFFUTT AFB, NE 68113 (NAICS 921190). OSHA activity number 341962504.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch United States AIR Force 55 Wing Offutt AIR Force Base — free Get an email when a new federal OSHA severe-injury report for United States AIR Force 55 Wing Offutt AIR Force Base is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 500 - STRATCOM
City
OFFUTT AFB
State
NE
ZIP
68113
Mailing
513 SAC BLVD. SUITE 201, OFFUTT AFB, NE 68113
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Case closed
Last modified
Data loaded
NAICS code
921190
Employees
5000
Ownership type
A

2 citations on file for this inspection.

1910.269 D02 IV

Serious Gravity 10 1 instance 4 exposed
Issued
May 17, 2017
Abate by
Sep 6, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.269(d)(2)(iv): The procedure did not clearly and specifically outline the scope, purpose, responsibility, authorization, rules, and techniques to be applied to the control of hazardous energy, and the measures to enforce compliance:    Offutt AFB, on 7 December 2016, the employer (55th Wing) did not direct in the squadron level checklist attached to the Form 269 that the employees review a schematic diagram of the electrical connection between the A & B sides of the 13,800V switch in annex building 500 of the old USSTRATCOM facility prior to their engaging in the safe clearance and Lock Out Tag Out procedures, during which an arc flash occurred.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 L08 II

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
May 17, 2017
Abate by
Jun 13, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.269(l)(8)(ii): For each employee exposed to hazards from electric arcs, the employer did not make a reasonable estimate of the incident heat energy to which the employee would be exposed.    The employer is failing to ensure that all employees exposed to electric arc hazards are aware of potential heat energy to which they may be exposed.  This most recently occurred on December 7, 2016 on the jobsite located on Offutt Air Force Base.  Civil Engineer employees were working on a 13,800V switch in annex building 500 of the old U.S. Strategic Command facility where there was an arc flash incident.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View United States AIR Force 55 Wing Offutt AIR Force Base's full OSHA safety record →