OSHA Inspection: KRAFT HEINZ

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of KRAFT HEINZ in 2504 INDUSTRIAL RD, KIRKSVILLE, MO 63501 (NAICS 311612). OSHA activity number 341974418.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kraft Heinz — free Get an email when a new federal OSHA severe-injury report for Kraft Heinz is published. One employer, no account, unsubscribe in one click.
Establishment
KRAFT HEINZ
Site address
2504 INDUSTRIAL RD
City
KIRKSVILLE
State
MO
ZIP
63501
Mailing
2504 INDUSTRIAL RD, KIRKSVILLE, MO 63501
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311612
Employees
480
Ownership type
A

3 citations on file for this inspection.

1910.119 J05

Deleted Serious Gravity 10 1 instance 12 exposed
Issued
May 22, 2017
Abate by
Jul 10, 2017
Penalty
Initial $12,675 · Current $0 Reduced

Hazardous substances 0170

29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) before use  The employer is failing to protect employees from hazards associated with ammonia leaks.  This was most recently documented at the Kraft-Heinz facility located at 2504 Industrial Road in Kirksville, Missouri.  The employer is allowing ice and rust accumulation on process equipment preventing visual inspection and compromising the integrity and operation of the system.    A.  An evaluation for ice accumulation had not been performed in all locations for remediation.  Ice accumulations were discovered in the following locations:  Valve HTLT - 09 (liquid transfer pump) Valve LTLT - 09 (Hansen valve) Compressor 3, Valve C3-01  Engine room Old System West Room  Compressor 1, Valve C1-01 Engine room Old System West Room  Lo temp accumulator (LTL pump vent #1 and LTL pump #1 suction)  High temperature NH3 accumulator   B.  An evaluation for corrosion had not been performed in all locations for remediation.  Corrosion issues were discovered in the following locations:  Valve HTLT - 13  Pump HTL transfer system HTLT-03 Pipe on top of the HTL system that goes to the accumulator Evaporator condenser EC9-11, Hansen 100 D Condenser 2 EC2-05
Recent events (2)
  • — I (S) $0
  • — Z (S) $12675

1910.303 G02 I

Deleted Serious Gravity 5 1 instance 12 exposed
Issued
May 22, 2017
Penalty
Initial $7,243 · Current $0 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):   Employees were exposed to an electrical shock hazard.  Employees working on or in the area of the electrical control box for compressor #1 in the legacy engine room were exposed to live conductors.   The 110 volt control box was not covered to prevent contact with live conductors.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7243

1910.305 G02 III

Deleted Serious Gravity 1 1 instance 12 exposed
Issued
May 22, 2017
Penalty
Initial $5,432 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:(a)(LOCATION)(IDENTIFY EQUIPMENT AND CONDITION(S))(STATE HAZARD(S) TO EMPLOYEE(S)NOTE: KNOTS IN CORDS, WINDING WITH TAPE, SPECIAL FITTINGS OR OTHER APPROVED MEANS OF CONNECTION ARE ACCEPTABLE (NEC 40010) 1910  Employees were exposed to an electrical shock hazard.  Employees working under the Legacy chillers area were exposed to live conductors from an electrical extension that feed the sump pump.   The 110 volt extension cord was broken at the fitting and attached with electrical tape that do not prevent contact with live conductors.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5432

View Kraft Heinz's full OSHA safety record →