Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: KEYSTONE PAPER & BOX COMPANY, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of KEYSTONE PAPER & BOX COMPANY, INC. in 31 EDWIN ROAD, SOUTH WINDSOR, CT 06074 (NAICS 322130). OSHA activity number 341987022.

Watch Keystone Paper & BOX Company, INC. — free Get an email when a new federal OSHA severe-injury report for Keystone Paper & BOX Company, INC. is published. One employer, no account, unsubscribe in one click.
Site address
31 EDWIN ROAD
City
SOUTH WINDSOR
State
CT
ZIP
06074
Mailing
31 EDWIN ROAD, SOUTH WINDSOR, CT 06074
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322130
Employees
53
Ownership type
A

5 citations on file for this inspection.

1910.215 A04

Serious Gravity 5 2 instances 6 exposed
Issued
Penalty
Initial $4664.00 · Current $2332.00 Reduced
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:     On, or about, December 20, 2016, in the following locations, the work rest provided on off-hand grinders had not been adjusted to within one eighth of an inch to the abrasive wheel:  A.  Maintenance Shop:  Sunex pedestal grinder. B.  Die Cutting:  Ryobi bench grinder.
Recent events (2)
  • — I (S) $2332
  • — Z (S) $4664

1910.332 B01

Repeat Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $13718.00 · Current $6859.00 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  Company:  On, or about, December 20, 2016, maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live diagnostic testing and when verifying whether or not electrical equipment was properly de-energized.  Keystone Paper & Box Company, Inc. was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA Inspection Number 516620, Citation Number 1, Item Number 12 and was affirmed as a Final Order on August 24, 2012, with respect to a workplace located at South Windsor, Connecticut.
Recent events (2)
  • — I (R) $6859
  • — Z (R) $13718

1910.335 A01 I

Repeat Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:   Company:  On, or about, December 20, 2016, personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, balaclavas, hard hats and hearing protection were not required to be worn by employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized.  Keystone Paper & Box Company, Inc. was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA Inspection Number 516620, Citation Number 1, Item Number 13b and was affirmed as a Final Order on August 24, 2012, with respect to a workplace located at South Windsor, Connecticut.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

1910.37 A03

Other-than-serious 1 instance 10 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:  Maintenance Shop:  On, or about, December 20, 2016, the exterior exit door was partially blocked by material, power equipment and a bucket.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.335 A01 II

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.335(a)(1)(ii): Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested:  Maintenance Shop:  On, or about, December 20, 2016, a pair of Salisbury Class 0 voltage rated gloves that were available for use had not been inspected since January, 2013.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View KEYSTONE PAPER & BOX COMPANY, INC.'s full OSHA safety record →