COLUMBIA, NC —
OSHA Inspection: STILETTO MANUFACTURING, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of STILETTO MANUFACTURING, INC. in 107 WATER STREET, COLUMBIA, NC 27925 (NAICS 336612). OSHA activity number 341991321.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STILETTO MANUFACTURING, INC.
- Site address
- 107 WATER STREET
- City
- COLUMBIA
- State
- NC
- ZIP
- 27925
- Mailing
- 107 WATER STREET, COLUMBIA, NC 27925
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336612
- Employees
- 9
- Ownership type
- A
Citations
15 citations on file for this inspection.
5(a)(1)
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $2,716 · Current $1,000 Reduced
General-duty citation text
Section 5(a)1: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazards. On or about December 20, 2016, the employer did not ensure a man-made oven being used to cure select chemical laminates onto sailboat parts conformed to the requirements outlined in NFPA 86 Standard for Ovens and Furnaces. ABATEMENT DOCUMENTATION REQUIRED
Recent events (3)
- — F (S) $1000
- — C (S) $2716
- — Z (S) $2716
1910.37 B04
- Issued
- Feb 6, 2017
- Penalty
- Initial $1,630 · Current $0 Reduced
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: On or about December 20, 2016, the employer did not ensure a direction exit sign was posted near the 2nd floor stairs which is the only exiting point. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $0
- — C (S) $1630
- — Z (S) $1630
1910.38 A
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.38(a): The emergency action plan required by 29 CFR 1910.157(a) or (b) when the employer has elected to partially or totally evacuate the workplace in the event of a fire emergency, or required by 29 CFR 1910.160(c)(1), did not cover the designated actions that the employer or employees must take to ensure employee safety from the fire and other emergencies: On or about December 20, 2016, the employer did not ensure a written emergency action evacuation plan was developed and implemented that covered the actions employees are to take in the event of an emergency. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.94 C04 II
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $2,173 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.94(c)(4)(ii): Spray rooms shall have noncombustible fire doors and shutters. Spray Room Area: On or about December 20, 2016, the entrance into the spray paint area was not equipped with a fire door shutters. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $1000
- — C (S) $2173
- — Z (S) $2173
1910.94 C04 IV
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.94(c)(4)(iv): Spray rooms used for production spray-finishing operations shall conform to the requirements for spray booths as outlined in 1910.107(b)1-(b)4 and (b)6 -(b)10: Spray Room Area: The employer did not ensure that the spray room area being used for production painting of boats conformed to all spray booth requirements. ABATEMENT CERTIFICATON REQUIRED
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.107 C06
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: Spray Room Area: On or about December 20, 2016, where spray rooms have to meet the specifications of spray booths for production spray finishing, the electrical installations such as, but not limited to outlets, lighting and ventilation fan motors did not conform to Class I Division I for hazardous locations. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.107 D02
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(d)(2): Spraying area(s) were not provided with mechanical ventilation adequate to remove flammable vapors, mists, or powders to a safe location and to confine and control combustible residues: Spray Room Area: On or about December 20, 2016, the employer did not ensure that the spraying area demarcated by plastic sheets hanging from ceiling trusses was provided with adequate ventilation to remove and prevent the buildup of flammable vapors and combustible residues. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.107 E09
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(e)(9): Grounding. Whenever flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) are transferred from one container to another, both containers shall be effectively bonded and grounded to prevent discharge sparks of static electricity: On or about December 20, 2016, where employees dispense flammable and combustible materials out of 55 gallon drums, the employer did not ensure that the drums and receiving containers were bonded and grounded to prevent the discharge of static electricity. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.134 C
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $1,630 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.134(c): The employer did not develop and implement a written respiratory protection program with required worksite-specific procedures and elements for required respirator use: On or about December 20, 2016, the employer did not implement a written respiratory protection program to ensure that employees who use respirators to perform operations such as but not limited to boat sanding, wipe downs and spray painting were trained in respirator use, cleanliness, fit tested and medically cleared to don such equipment. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $1000
- — C (S) $1630
- — Z (S) $1630
1910.151 C
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $2,173 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: On or about December 20, 2016, an eyewash station and safety shower was not provided for employees engaged in the use of corrosive materials such as, but not limited to the Endurance Technologies 9226B hardener. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $1000
- — C (S) $2173
- — Z (S) $2173
1910.253 B04 III
- Issued
- Feb 6, 2017
- Abate by
- Mar 3, 2017
- Penalty
- Initial $1,630 · Current $0 Reduced
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one half hour: Entrance area: On or about December 20, 2016, oxygen and acetylene cylinders were being stored together in a wooden box located near a side entrance. ABATEMENT CERTIFICATOIN REQUIRED
Recent events (3)
- — F (S) $0
- — C (S) $1630
- — Z (S) $1630
1910.1200 E01
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $1,630 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: On or about December 20, 2016, the employer did not maintain a hazard communication program and employees were not trained on the hazards associated with use of chemical components such as, but not limited to Ethyl Benzene 10%, Methyl n-amyl Ketone 50%, Bisphenol A Epoxy Resin 90%, Polyoxypropylenediame 95% and Denatured alcohol. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (S) $1000
- — C (S) $1630
- — Z (S) $1630
1910.132 D01
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): On or about December 20, 2016, the employer did not ensure that a written hazard assessment for personal protective equipment had been conducted for all employees engaged in boat building operations. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
1910.141 D02 II
- Issued
- Feb 6, 2017
- Abate by
- Mar 3, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.141(d)(2)(ii): Lavatories were not provided with hot and cold, or tepid running water: Manager's Office Restroom: On or about December 20, 2016, the employer did not ensure that sink being used by employees had hot or tepid running water. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
1910.303 B02
- Issued
- Feb 6, 2017
- Abate by
- Mar 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about 12/20/2016, the employer did not ensure that a Dyna-Glo kerosene and electrical portable forced air heater was not properly ventilated while being used indoors as part of a heat treat process to cure laminate materials. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Stiletto Manufacturing, INC.
View Stiletto Manufacturing, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 336612)
More inspections in NC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341991321.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.