Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: AIR FORCE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AIR FORCE in 8574 SIJAN AVE, JBER, AK 99506 (NAICS 488119). OSHA activity number 342007309.

Watch AIR Force — free Get an email when a new federal OSHA severe-injury report for AIR Force is published. One employer, no account, unsubscribe in one click.
Establishment
AIR FORCE
Site address
8574 SIJAN AVE
City
JBER
State
AK
ZIP
99506
Mailing
10441 KUTER AVE, JBER, AK 99506
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488119
Employees
32
Ownership type
D

4 citations on file for this inspection.

1910.244 A01 II

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.244(a)(1)(ii): Rated load(s) of portable jack(s) were not legibly and permanently marked in a prominent location on the jack(s) by casting, stamping, or other suitable means.  Building 8574, East bay; on or about 03 January 2017 and times prior thereto; a blue floor jack, labeled SO36, model number YA657C, serial number SS090200967 did not have the load rating prominently marked. This condition exposed employees to a caught under hazard.
Recent events (1)
  • — Z (S) $0

1910.303 B07 IV

Serious Gravity 1 3 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7)(iv): Electric equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.  Buildings 8549 and 8574; on or about 03 January 2017 and times prior thereto; three instances were noted were electrical outlets were damaged:       a. Building 8549, Break room, a 120 volt energized electrical outlet had a cracked receptacle.        b. Building 8574, North wall adjacent to boiler room, an energized electrical outlet box was cracked on the left hand side.       c. Building 8574, Communications room, an electrical thermostat control was damaged. The control switch was separated from the outlet box exposing energized wiring.  This condition exposed employees to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors.  Building 8574, South bay, on or about 03 January 2017 and times prior thereto; a 50-foot energized extension cord was routed through wall and ceiling openings. This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Repeat Gravity 1 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  Building 8549; on or about 03 January 2017 and times prior thereto; the employer did not ensure that electrical openings were effectively closed. Two instances were noted:       a. Cage Area, an energized 120/208, Heavy Duty Switch Box had a knockout plug missing on the lower right hand side.        b. West Wall, an energized Curtis Air Compressor had a knockout plug missing on the power control box.  This condition exposed employees to an electrical shock and electrical burn hazards.  The Joint Base Elmendorf-Richardson was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(b)(1)(ii), which was contained in OSHA inspection number 952426, citation number 1, item number 2a and was affirmed as a final order on 19 March 2014, with respect to a workplace located at 3rd MXS AGE Building 8549 located at JBER, Alaska.