BATAVIA, IL —
OSHA Inspection: GREENSEED CONTRACT PACKAGING, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of GREENSEED CONTRACT PACKAGING, INC. in 1025 PARAMOUNT PARKWAY, BATAVIA, IL 60510 (NAICS 311423). OSHA activity number 342018918.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GREENSEED CONTRACT PACKAGING, INC.
- Site address
- 1025 PARAMOUNT PARKWAY
- City
- BATAVIA
- State
- IL
- ZIP
- 60510
- Mailing
- 1025 PARAMOUNT PARKWAY, BATAVIA, IL 60510
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311423
- Employees
- 90
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.28 B02 I
- Issued
- Jun 7, 2017
- Penalty
- Initial $6,338 · Current $3,732 Reduced
General-duty citation text
1910.28(b)(2)(i) The employer must ensure that each employee in a hoist area is protected from falling 4 feet (1.2 m) or more to a lower level by a guardrail system, a personal fall arrest system, or a travel restraint system as required by 29 CFR 1910.28(b)(2)(i)(A) to 29 CFR 1910.28(b)(2)(i)(C). Packaging lines department, overhead product receiving mezzanines: on or about January 25, 2017, employees (product dumpers) receiving palletized products at the overhead mezzanines were exposed to fall hazards over 9 feet likely to result in serious injury. Employees were assigned to remove horizontal chain at the edge of the platform without fall protection provided to allow for forklift operator to place load in the area. There is no abatement documentation or certification required for this item.
Recent events (2)
- — I (S) $3732
- — Z (S) $6338
1910.147 C06 I
- Issued
- Jun 7, 2017
- Abate by
- Jul 14, 2017
- Penalty
- Initial $6,338 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct an annual or more frequent inspection of the energy control procedure to ensure that the procedure and requirements of this standard were followed: Packaging lines department, packaging line no. 2, Hayssen Flexible Systems Pro Former: on or about January 11, 2017, the employer did not conduct, at least once per year, periodic inspection to identify and correct hazardous energy control (lockout) deviations or inadequacies in procedures and methods. Operators and maintenance personnel were regularly unjamming and re-feeding foil (servicing tasks) in the point-of-operation and associated danger zone on energized equipment while permitted to use a provided key to by-pass access doors safety interlocks. Employees had their fingers and hands exposed to machine caught-in hazards likely to result in serious injury. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $3733
- — Z (S) $6338
1910.147 D
- Issued
- Jun 7, 2017
- Abate by
- Jul 14, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(d): The established procedure for the application of energy control (the lockout or tagout procedures) did not cover the actions listed in and was not done in sequence as required by 29 CFR 1910.147(d)(1)-(6): Packaging lines department, packaging line no. 2, Hayssen Flexible Systems Pro Former: on or about January 11, 2017, operators and maintenance personnel performing regular unjamming and re-feeding foil (servicing tasks) in the point-of-operation and associated danger zones were not required to apply energy controls in the following sequence prior to starting work: (a) prepare for shut down by recognizing energy hazards and its controls, (b) turn off and shut down the machines, (c) physically locate and operate energy isolating devices in such a manner as to isolate the machine or equipment from the energy source, (d) affix lockout or tagout devices to each energy isolating device, (e) render safe all potentially hazardous stored or residual energy, (f) verify that isolation and de-energization of the machine or equipment have been accomplished. Employees assigned to perform servicing tasks on energized equipment were provided with a by-pass key to override access doors safety interlocks and had their hands and fingers exposed to machine caught-in hazards likely to result in serious injury where hazardous energy control (lockout/tagout) was not implemented. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Jun 7, 2017
- Abate by
- Jul 14, 2017
- Penalty
- Initial $5,070 · Current $2,535 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. Packaging lines department, packaging line no. 5, checker no. 02, quad electrical box and overhead flexible electrical cords: on or about January 11, 2017, employees were handling energized electrical box to connect checker no. 02. Subject electrical box was not designed, constructed, and intended for current installation and use with a flexible drop cord zip-tied to building's structural member without strain-relief. Employees were exposed to fire and electrical hazards likely to result in serious injury. Abatement certification is required of this item in accordance with the requirement of 29 CFR 1903.19(c).
Recent events (2)
- — I (S) $2535
- — Z (S) $5070
1910.305 G01 IV A
- Issued
- Jun 7, 2017
- Abate by
- Jul 14, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Packaging lines department, packaging lines, overhead flexible electrical cords: on or about January 11, 2017, employees were assigned to operate and work with equipment powered by energized flexible cords connected in series to each other and to building's structures with zip ties in lieu of permanent wiring. Employees were exposed to fire and electrical hazards likely to result in serious injury. Abatement certification is required of this item in accordance with the requirement of 29 CFR 1903.19(c).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Jun 7, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. Packaging lines department, cafeteria, wall mounted light switch electrical box: on or about January 11, 2017, employees were exposed to contact with live wires when turning on/off ceiling light and walking through the entry door next to the exposed energized light switch electrical box with a missing faceplate and a knockout where drywall opening was cut out. There is no abatement certification or documentation required for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 311423)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342018918.