SAGINAW, TX —
OSHA Inspection: 2ND CHANCE PALLETS LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of 2ND CHANCE PALLETS LLC in 213 E MCLEROY BLVD, SAGINAW, TX 76179 (NAICS 423310). OSHA activity number 342020138.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- 2ND CHANCE PALLETS LLC
- Site address
- 213 E MCLEROY BLVD
- City
- SAGINAW
- State
- TX
- ZIP
- 76179
- Mailing
- 213 E MCLEROY BLVD, SAGINAW, TX 76179
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423310
- Employees
- 29
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.178 L01 I
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $8,873 · Current $0 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l). The employer failed to ensure that employees operating forklifts throughout the plant were trained, exposing employees to struck by hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $8873
1910.213 D01
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $6,338 · Current $4,272 Reduced
General-duty citation text
29 CFR 1910.213(d)(1): Circular handfed crosscut table saw(s) were not guarded by an automatically adjusting hood which completely enclosed that portion of the saw above the table and above the material being cut. In the saw department, employees operating an unguarded table saw were exposed to amputation hazards.
Recent events (2)
- — I (S) $4272
- — Z (S) $6338
1910.303 B07 IV
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $5,070 · Current $3,296 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating In the Repair Department, the electrical extension cord used to energize the DeWalt grinder outer jacket was damaged exposing employees to electrical shock hazards.
Recent events (2)
- — I (S) $3296
- — Z (S) $5070
1910.334 A02 I
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): In the Repair Department, the electrical extension cord used to energize the DeWalt grinder outer jacket was damaged exposing employees to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $5,070 · Current $3,296 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment. a) In the plant near the Rebuild Department, there were 3 electrical panels blocked by welding equipment and cleaning supplies exposing employees to electrical and fire hazards. b) In the plant at the far end past the Dismantling department, 2 electrical panels were blocked by stock and by portable tools exposing employees to electrical and fire hazards.
Recent events (2)
- — I (O) $3296
- — Z (S) $5070
1910.305 B01 II
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $5,070 · Current $3,296 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. a) On the east wall in the Rebuild department by the electrical panel boxes, the employer has a 4-plex metal receptacle that has an unused opening on the side not closed, exposing employees to electrical shock hazard. b) The control box to the "Notcher" machine has an unused opening on the front side, exposing employees to electrical shock hazard. c) The control box to the "Hawg" saw has an unused opening on the front side, exposing employees to electrical shock hazard.
Recent events (2)
- — I (S) $3296
- — Z (S) $5070
1910.305 G01 IV A
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $7,605 · Current $4,943 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. a) In the Repair Department, an extension cord ran across the floor to energize another cord to energize a power tap in lieu of permanent wiring, exposing employees to electrical shock and fire hazards. b) In the Saw Department, several extension cords ran across the floor up underneath machinery to energize another cord to energize certain machines in lieu of permanent wiring, exposing employees to electrical shock and fire hazards.
Recent events (2)
- — I (S) $4943
- — Z (S) $7605
1910.305 G02 III
- Issued
- Jun 28, 2017
- Abate by
- Jul 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. The employer failed to ensure that the orange electrical extension cord located near the "Dismantler" used to energize the saw had been pulled away at the strain relief, exposing employees to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at 2ND Chance Pallets LLC
View 2ND Chance Pallets LLC's full OSHA safety record →
More inspections in this industry (NAICS 423310)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342020138.