JASPER, GA —
OSHA Inspection: GOVERMENT RESOURCE PACKAGING PRODUCT, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of GOVERMENT RESOURCE PACKAGING PRODUCT, LLC in 359 HOOD RD, JASPER, GA 30143 (NAICS 322211). OSHA activity number 342022043.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GOVERMENT RESOURCE PACKAGING PRODUCT, LLC
- Site address
- 359 HOOD RD
- City
- JASPER
- State
- GA
- ZIP
- 30143
- Mailing
- 359 HOOD RD, JASPER, GA 30143
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322211
- Employees
- 3
- Ownership type
- A
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Mar 17, 2017
- Abate by
- Apr 12, 2017
- Penalty
- Initial $3,803 · Current $0 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees: On or about 1/9/17 in the warehouse area: Employees were exposed to a laceration and amputation hazard from the Slitter Machine (SN. 297); the e-stop was located only at one end not readily accessible, employee would to travel 11-feet to the e-stop in case of an emergency. Among other methods, one feasible and acceptable abatement method to correct this hazard is to follow the National Fire Protection Association (NFPA) 79, Electrical Standard for Industrial Machinery, 2012 Edition. Stop and Emergency Stop push buttons shall be continuously operable and readily accessible in accordance with the guidelines set forth in NFPA 79, Article 10.7 .1 Location and Operation.
Recent events (2)
- — I (S) $0
- — Z (S) $3803
1910.178 L01 II
- Issued
- Mar 17, 2017
- Abate by
- Apr 12, 2017
- Penalty
- Initial $3,803 · Current $2,660 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(ii): The employer did not ensure that each operator had successfully completed the training required by paragraph (l), except as permitted by paragraph (l)(5), prior to permitting an employee to operate: On or about 1/9/17 in the warehouse: The employer did not ensure that the powered industrial truck operators were trained prior to operation.
Recent events (2)
- — I (O) $2660
- — Z (S) $3803
1910.212 A03 II
- Issued
- Mar 17, 2017
- Abate by
- Apr 12, 2017
- Penalty
- Initial $3,803 · Current $2,660 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): On or about 1/9/17 in the warehouse area: Employees were exposed to a laceration and amputation hazard from the Slitter Machine (SN. 297); the employer failed to ensure that the rollers shafts was guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operations. The unguarded opening was 33-inch x 11-foot opening not guarded while cutting card board boxes.
Recent events (2)
- — I (S) $2660
- — Z (S) $3803
1910.303 G02 I
- Issued
- Mar 17, 2017
- Abate by
- Apr 12, 2017
- Penalty
- Initial $3,803 · Current $2,660 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): On or about 1/9/17 located in warehouse area, the Gluer machine (SR M-1555) electrical conduit box cover was missing with exposed conductors; the employer failed to replace the cover to guard against accidents from employees hitting the conductors while operating the Glue machine.
Recent events (2)
- — I (O) $2660
- — Z (S) $3803
1910.305 G02 II
- Issued
- Mar 17, 2017
- Abate by
- Apr 12, 2017
- Penalty
- Initial $3,803 · Current $2,660 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Hard-service cord and junior hard-service cord No. 14 and larger were repaired by splicing, which did not retain the insulation, outer sheath properties, and usage characteristics of the cord that was spliced:Note: Hard service flexible cords No. 12 or larger may be spliced if the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. On or about 1/9/17 located in warehouse area Printer (SR 509), the Printer service electrical power cord had exposed conductors without any insulation where a splice was located; wire nuts caps were missing and hot conductors was an accident waiting to helping by the employees rubbing against the naked wires.
Recent events (2)
- — I (S) $2660
- — Z (S) $3803
More inspections in this industry (NAICS 322211)