OSHA Inspection: RBK-II, INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of RBK-II, INC. in 200 TIGUE ST, DUNMORE, PA 18512 (NAICS 238210). OSHA activity number 342023843.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Rbk-Ii, INC. — free Get an email when a new federal OSHA severe-injury report for Rbk-Ii, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
RBK-II, INC.
Site address
200 TIGUE ST
City
DUNMORE
State
PA
ZIP
18512
Mailing
624 FELLOWS ST, SCRANTON, PA 18512
Inspection type
Unprogrammed Related (G)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

4 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 5 exposed
Issued
Apr 19, 2017
Abate by
May 1, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a) Old boiler room: A relocatable power tap was installed and used provide additional receptacles for a temporary electrical system. This device, which is not intended for use on a construction site, exposed employees to a potential electric shock and fire hazard, on or about January 10, 2017.  b) Dunmore, PA: A relocatable power tap was connected to the end of an extension cord and used as additional receptacles in a temporary electrical system. This device, which is not intended for use on a construction site or while plugged into an extension cord, exposed employees to a potential electric shock and fire hazard, on or about January 10, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.404 B01 I

Serious Gravity 5 1 instance 12 exposed
Issued
Apr 19, 2017
Abate by
May 1, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.404(b)(1)(i): The employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites:  a) Dunmore, PA: This employer did not provide ground fault circuit protection for employees, including those of several subcontractors, who were exposed to electric shock hazards while using extension cords and power tools on a construction site, on or about January 10, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.405 D

Serious Gravity 10 1 instance 6 exposed
Issued
Apr 19, 2017
Abate by
May 1, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:  a) Dunmore, PA: Employees were exposed to an electric shock hazard while working in close proximity to or while resetting breakers in a 200-amp panel box that was not equipped with a dead front or otherwise protected, on or out March 2, 2017.  ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.501 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 19, 2017
Abate by
May 1, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.501(b)(1): Each employee on a walking/working surface (horizontal and vertical surface) with an unprotected side or edge which is 6 feet (1.8 m) or more above a lower level were not protected from falling by the use of guardrail systems, safety net systems, or personal fall arrest systems:  a) Dunmore, PA: Employees were exposed to a fall hazard while installed Romex cable along the ceiling of the hotel balconies, which were not equipped with guardrails, discovered on about January 23, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0