DUNMORE, PA —
OSHA Inspection: RBK-II, INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of RBK-II, INC. in 200 TIGUE ST, DUNMORE, PA 18512 (NAICS 238210). OSHA activity number 342023843.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RBK-II, INC.
- Site address
- 200 TIGUE ST
- City
- DUNMORE
- State
- PA
- ZIP
- 18512
- Mailing
- 624 FELLOWS ST, SCRANTON, PA 18512
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 2
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.403 B02
- Issued
- Apr 19, 2017
- Abate by
- May 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) Old boiler room: A relocatable power tap was installed and used provide additional receptacles for a temporary electrical system. This device, which is not intended for use on a construction site, exposed employees to a potential electric shock and fire hazard, on or about January 10, 2017. b) Dunmore, PA: A relocatable power tap was connected to the end of an extension cord and used as additional receptacles in a temporary electrical system. This device, which is not intended for use on a construction site or while plugged into an extension cord, exposed employees to a potential electric shock and fire hazard, on or about January 10, 2017. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $0
1926.404 B01 I
- Issued
- Apr 19, 2017
- Abate by
- May 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.404(b)(1)(i): The employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites: a) Dunmore, PA: This employer did not provide ground fault circuit protection for employees, including those of several subcontractors, who were exposed to electric shock hazards while using extension cords and power tools on a construction site, on or about January 10, 2017. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $0
1926.405 D
- Issued
- Apr 19, 2017
- Abate by
- May 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front: a) Dunmore, PA: Employees were exposed to an electric shock hazard while working in close proximity to or while resetting breakers in a 200-amp panel box that was not equipped with a dead front or otherwise protected, on or out March 2, 2017. ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED
Recent events (1)
- — Z (S) $0
1926.501 B01
- Issued
- Apr 19, 2017
- Abate by
- May 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.501(b)(1): Each employee on a walking/working surface (horizontal and vertical surface) with an unprotected side or edge which is 6 feet (1.8 m) or more above a lower level were not protected from falling by the use of guardrail systems, safety net systems, or personal fall arrest systems: a) Dunmore, PA: Employees were exposed to a fall hazard while installed Romex cable along the ceiling of the hotel balconies, which were not equipped with guardrails, discovered on about January 23, 2017. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 238210)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342023843.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.