Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: A-1 ELECTRIC LTD

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of A-1 ELECTRIC LTD in 790 S. BUCHANNAN, AMARILLO, TX 79106 (NAICS 238210). OSHA activity number 342046901.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch A-1 Electric LTD — free Get an email when a new federal OSHA severe-injury report for A-1 Electric LTD is published. One employer, no account, unsubscribe in one click.
Establishment
A-1 ELECTRIC LTD
Site address
790 S. BUCHANNAN
City
AMARILLO
State
TX
ZIP
79106
Mailing
DRAWER 3340, AMARILLO, TX 79116
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
35
Ownership type
A

5 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 30 exposed
Issued
Jul 19, 2017
Abate by
Aug 9, 2017
Penalty
Initial $12,675 · Current $0 Reduced
OSH ACT of 1970 Section (5)(a)(1):   The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees that were exposed to an arc flash hazard:  On or about January 21, 2017, on the second floor in the electrical room, employees pulling wire near an energized 480V Busway were exposed to arc flash and electrical shock hazards.
Recent events (3)
  • — J (S) $0
  • — C (S) $12675
  • — Z (S) $12675

1926.95 A

Deleted Serious Gravity 10 2 instances 3 exposed
Issued
Jul 19, 2017
Abate by
Aug 9, 2017
Penalty
Initial $12,675 · Current $0 Reduced
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided:  At the job site located at 790 S. Buchanan in Amarillo, Texas employees were not provided with appropriate electrical protective equipment to prevent burns from exposure to an arc-flash incident, or contact with exposed and energized electrical parts while working with energized circuits.   1) On or about January 21, 2017 and times prior thereto, while drilling holes for the disconnect plug at the 480V/3000 Amp Busway.  2) On or about April 6 2017 and times prior thereto, while pulling wire into the breaker panel in the main electric room on the first floor.
Recent events (3)
  • — J (S) $0
  • — C (S) $12675
  • — Z (S) $12675

1926.405 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Jul 19, 2017
Abate by
Aug 9, 2017
Penalty
Initial $12,675 · Current $12,675
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:  On or about April 5, 2017 and at times prior thereto, employees performing electrical work on temporary power taps located on the first floor containing breaker boxes with unused openings were exposed to electrical shock hazards.
Recent events (3)
  • — J (S) $12675
  • — C (S) $12675
  • — Z (S) $12675

1926.416 A01

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Jul 19, 2017
Abate by
Aug 9, 2017
Penalty
Initial $12,675 · Current $0 Reduced
29 CFR 1926.416(a)(1):  Employees were permitted to work in close proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  On or about January 21, 2017 and times prior thereto, employees installing a disconnect plug in the electrical room on the second floor next to the energized 480 volt Busway were exposed to electrical shock and arc flash/blast hazards.
Recent events (3)
  • — J (S) $0
  • — C (S) $12675
  • — Z (S) $12675

1926.416 A03

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Jul 19, 2017
Abate by
Aug 9, 2017
Penalty
Initial $12,675 · Current $0 Reduced
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into pysical or electrical contact with the electric power circuit:  On or about January 21, 2017 and times prior thereto, the employer did not ascertain a circuit was de-energized prior to employees installing a disconnect plug in the electrical room on the second floor and exposed them to electrical shock and arc flash/blast hazards.
Recent events (3)
  • — J (S) $0
  • — C (S) $12675
  • — Z (S) $12675

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342046901.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.